Apparel & Footwear Wholesale Market – Excessive Neutral Current & Harmonic Distortion

APF harmonic mitigation case

Industry
Apparel & footwear wholesale Market
Main load
LED lighting / LED display screens
Transformer
2500 kVA
APF installation
2 × 200 A
Measurement load rate
90%
Existing compensation
600 kvar

1. Project Background

The building has eight floors. Floors 1–2 contain a large number of shops, and the main floor loads are LED lighting. Property management reported that, when the three phase currents were similar, the neutral-line current at the Floor 1 and Floor 2 main switches was higher than the phase current. Because the neutral conductor was smaller than the phase conductors, long-term operation presented an overheating and fire risk.

The transformer circuit is rated at 2500 kVA. The main equipment includes LED lighting and LED display screens. The circuit is equipped with two compensation cabinets with a total capacity of 600 kvar. During measurement, the load rate was 90%. One 200 A APF was installed at the Floor 1 main incoming switch and one at the Floor 2 main incoming switch.

2. Measurement Purpose

The measurement was carried out after the two 200 A APFs on the Floor 1 and Floor 2 main incoming switches were put into operation, to verify whether the filtering effect met the expected result.

3. Floor 1 Measured Results

APF status 3rd (A) 5th (A) 7th (A) THD (A) N-line (A) ITHD VTHD
Off 133.02 39.88 20.29 141.77 367.6 52.64% 5.30%
On 9.02 5.38 3.54 16.88 25.19 5.08% 4.05%

4. Floor 2 Measured Results

APF status 3rd (A) 5th (A) 7th (A) THD (A) N-line (A) ITHD VTHD
Off 135.42 39.93 27.88 145.41 360.6 58.24% 5.30%
On 6.14 8.22 6.93 17.4 19.54 6.88% 4.05%

5. Main Incoming Switch Measured Results

APF status 3rd (A) 5th (A) 7th (A) THD (A) N-line (A) ITHD VTHD
Off 842.4 199.83 132.55 850.7 2245.7 40.85% 5%
On 671 181.9 77.38 704.1 1733 33.12% 4.20%

6. Result Summary

  • For the Floor 1 main switch, the report states that the zero-sequence harmonic mitigation effect after the APF was put into operation was very obvious, and the filter display data were basically consistent with the measured data.
  • For the Floor 2 main switch, the report gives the same conclusion: the zero-sequence harmonic mitigation effect was very obvious, and the filter display data were basically consistent with the measured data.
  • At the main incoming switch, after the APFs on Floors 1 and 2 were put into operation, the N-line apparent current decreased from 2245.7 A to 1733 A, a reduction of 512.7 A in zero-sequence harmonic current.
  • The report states that, if the total-circuit harmonic current is to be reduced to the ideal effect, sufficient APF capacity needs to be installed at each floor and in the main distribution room.

7. Filter Display Records

The report states that the filter display data were basically consistent with the measured data.

Filter-screen records before and after treatment.

8. Conclusion

The report concludes that the filtering retrofit results from installing active power filters at the Floor 1 and Floor 2 main switches were relatively satisfactory and met the acceptance conditions.