Fast Switching Response
Initial response is less than 20 ms and continuous response is less than 40 ms, supporting rapidly changing reactive power demand.
NHKCS
Thyristor Switch
A contactless capacitor-bank switch for compensation systems that require fast and frequent changes in reactive power output.
Product Advantages
Initial response is less than 20 ms and continuous response is less than 40 ms, supporting rapidly changing reactive power demand.
Electronic switching reduces the disturbance associated with capacitor-step switching in the power system.
Thyristor switching avoids mechanical contact wear and supports a long switching service life.
The contactless design suits applications with repeated changes in load, including lifting, welding and forming equipment.
Supports pure-capacitor banks and capacitor-reactor combinations with series reactor ratios up to 14%.
Supports symmetrical three-phase compensation and individual-phase step compensation.
The DC 8-16 V control input can operate with compatible reactive power controllers, PLCs and process-control equipment.
Vertical or horizontal installation is supported when the specified fan-side and exhaust clearances are maintained.
Compensation systems that need capacitor-bank switching with an initial response of less than 20 ms
Loads with repeated changes where a contactless thyristor switch is specified
Welding processes that require frequent capacitor-step switching
Forming machines with rapidly changing reactive power demand
Banks that would subject mechanical contacts to high switching rates
Capacitor banks without a series reactor, within the stated ratings
Capacitor-reactor combinations with series reactor ratios up to 14%
Single-phase capacity up to 15 kvar for individual-phase steps
DC 8–16 V control input for compatible reactive power controllers, PLCs and process-control equipment
Compensation assemblies that keep the specified fan-side and exhaust clearances
| Nominal Voltage | Voltage Range | Control Input | Voltage THD | Power Loss |
|---|---|---|---|---|
| 400 V, 50/60 Hz | Un ±10% | DC 8-16 V | Max. 5% | Approx. 2 W/A |
| Three Phase Capacity | Single Phase Capacity | Initial Response | Continuous Response |
|---|---|---|---|
| Max. 60 kvar | Max. 15 kvar | <20 ms | <40 ms |
Common Specifications
Supports pure-capacitor banks and capacitor-reactor combinations with series reactor ratios up to 14%.
Symmetrical three-phase and individual-phase step compensation.
| Protection Class | Degree of Protection | Electrical Safety | Dimensions W × H × D | Weight |
|---|---|---|---|---|
| Class I | IP10 | EN 61010:2001 · Pollution Degree II · CAT III | 116 × 187 × 170 mm | Approx. 2500 g |
Common Specifications
Vertical or horizontal mounting. Fan-side clearance: >50 mm; exhaust-side clearance: >150 mm.
Install as part of a compensation assembly with suitable upstream protection and isolation.
| Ambient Temperature | Storage Temperature | Relative Humidity |
|---|---|---|
| -20°C to +55°C | -25°C to +70°C | 5-95%, non-condensing |
You can also attach drawings, product photos or test reports, if available.
Choose it when reactive power demand changes quickly and capacitor steps need fast, frequent switching. Typical applications listed in the manual include cranes, lifting equipment, welding equipment and forming machinery.
Yes. The manual covers plain capacitor banks and capacitor banks with series reactor ratios up to 14%. The reactor and capacitor must still be selected for the site’s harmonic conditions.
Yes. It supports symmetrical three-phase compensation and individual-phase step compensation. The standard manual lists a maximum load of 60 kvar for three-phase use and 15 kvar for single-phase use; confirm the supplied unit’s nameplate before selection.
The specified control input is DC 8–16 V. Check the controller output and wiring before ordering.
The manual specifies an initial response time below 20 ms and a continuous response time below 40 ms. System-level response also depends on the controller and compensation settings.
No. The manual requires a series-connected disconnecting and protective device. It also specifies ventilation clearances of more than 50 mm on the fan side and more than 150 mm on the exhaust side.