NHKCS

Thyristor Switch

Thyristor Switch

A contactless capacitor-bank switch for compensation systems that require fast and frequent changes in reactive power output.

Product Advantages

  • 400 V Nominal Voltage, 50/60 Hz
  • <20 ms Initial Response
  • Max. 60 kvar Three-Phase Capacity
  • 116 × 187 × 170 mm Dimensions

Core Advantages

Fast Switching Response

Initial response is less than 20 ms and continuous response is less than 40 ms, supporting rapidly changing reactive power demand.

Low Switching Disturbance

Electronic switching reduces the disturbance associated with capacitor-step switching in the power system.

No Mechanical Contact Wear

Thyristor switching avoids mechanical contact wear and supports a long switching service life.

Suitable for Frequent Switching

The contactless design suits applications with repeated changes in load, including lifting, welding and forming equipment.

Pure Capacitor and Detuned Systems

Supports pure-capacitor banks and capacitor-reactor combinations with series reactor ratios up to 14%.

Three Phase and Individual Phase Compensation

Supports symmetrical three-phase compensation and individual-phase step compensation.

Control System Integration

The DC 8-16 V control input can operate with compatible reactive power controllers, PLCs and process-control equipment.

Flexible Mounting Orientation

Vertical or horizontal installation is supported when the specified fan-side and exhaust clearances are maintained.

Product Applications

Fast-changing reactive power demand

Compensation systems that need capacitor-bank switching with an initial response of less than 20 ms

Lifting equipment

Loads with repeated changes where a contactless thyristor switch is specified

Welding equipment

Welding processes that require frequent capacitor-step switching

Forming equipment

Forming machines with rapidly changing reactive power demand

Frequent capacitor-step switching

Banks that would subject mechanical contacts to high switching rates

Pure-capacitor compensation banks

Capacitor banks without a series reactor, within the stated ratings

Detuned capacitor-reactor systems

Capacitor-reactor combinations with series reactor ratios up to 14%

Individual-phase step compensation

Single-phase capacity up to 15 kvar for individual-phase steps

Controller and PLC integration

DC 8–16 V control input for compatible reactive power controllers, PLCs and process-control equipment

Vertical or horizontal assemblies

Compensation assemblies that keep the specified fan-side and exhaust clearances

Electrical Ratings

Nominal Voltage Voltage Range Control Input Voltage THD Power Loss
400 V, 50/60 Hz Un ±10% DC 8-16 V Max. 5% Approx. 2 W/A

Load and Switching Performance

Three Phase Capacity Single Phase Capacity Initial Response Continuous Response
Max. 60 kvar Max. 15 kvar <20 ms <40 ms

Common Specifications

Supports pure-capacitor banks and capacitor-reactor combinations with series reactor ratios up to 14%.

Symmetrical three-phase and individual-phase step compensation.

Safety and Installation

Protection Class Degree of Protection Electrical Safety Dimensions W × H × D Weight
Class I IP10 EN 61010:2001 · Pollution Degree II · CAT III 116 × 187 × 170 mm Approx. 2500 g

Common Specifications

Vertical or horizontal mounting. Fan-side clearance: >50 mm; exhaust-side clearance: >150 mm.

Install as part of a compensation assembly with suitable upstream protection and isolation.

Operating Conditions

Ambient Temperature Storage Temperature Relative Humidity
-20°C to +55°C -25°C to +70°C 5-95%, non-condensing

Please Share the Details You Know:

  • Product or model
  • Application or problem to solve
  • Required specifications, such as voltage, frequency or capacity
  • Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements

FAQ

When should I choose a thyristor switch for capacitor banks?

Choose it when reactive power demand changes quickly and capacitor steps need fast, frequent switching. Typical applications listed in the manual include cranes, lifting equipment, welding equipment and forming machinery.

Can it be used with both plain capacitor banks and detuned banks?

Yes. The manual covers plain capacitor banks and capacitor banks with series reactor ratios up to 14%. The reactor and capacitor must still be selected for the site’s harmonic conditions.

Does it support three-phase and individual-phase compensation?

Yes. It supports symmetrical three-phase compensation and individual-phase step compensation. The standard manual lists a maximum load of 60 kvar for three-phase use and 15 kvar for single-phase use; confirm the supplied unit’s nameplate before selection.

What control signal does it require?

The specified control input is DC 8–16 V. Check the controller output and wiring before ordering.

How quickly does it respond?

The manual specifies an initial response time below 20 ms and a continuous response time below 40 ms. System-level response also depends on the controller and compensation settings.

Can the switch replace the branch protection device?

No. The manual requires a series-connected disconnecting and protective device. It also specifies ventilation clearances of more than 50 mm on the fan side and more than 150 mm on the exhaust side.