Harmonic Mitigation for Industrial Kilns
PROJECT CASE
APPLICATION
Kiln Production Line |
SOLUTION
2 × 200 A SiC APF |
Project Challenge
An existing APF had not reduced the site’s harmonic distortion sufficiently. Persistent harmonics prevented the capacitor bank from switching normally and contributed to low power factor. Measurements were taken across the ball-mill and kiln circuits to locate the dominant harmonic source.
Diagnosis
Ball-mill circuits were ruled out as the primary source. The kiln circuits showed strong even harmonics; detailed testing identified the kilns as the main source, with the 2nd harmonic around 150 A and elevated 17th, 19th and 21st harmonics.

Kiln-load harmonic spectrum confirming significant even-harmonic content.
Solution
A 200 A silicon-carbide (SiC) active harmonic filter was installed beside each of the two kiln control cabinets, providing local compensation close to the harmonic source rather than relying only on upstream filtering.

Two 200 A SiC active harmonic filters installed next to the kiln control cabinets.
PROJECT OUTCOMES
Measured Improvement After Retrofit
Follow-up measurements at the low-voltage main incomer confirmed a clear improvement in power quality. Even harmonics were substantially reduced, while voltage and current waveforms moved much closer to sinusoidal conditions.
EVEN HARMONICS
2nd / 4th / 6th significantly reduced |
WAVEFORMS
Voltage and current close to sine waves |
FINAL MEASUREMENT
cosφ 0.976–0.983 |

Even harmonics after retrofit |

Voltage waveform after retrofit |

Current waveform after retrofit |

Final PF / cosφ measurement |
Post-retrofit field measurements showing lower even-harmonic content, improved waveforms, and final cosφ readings near 0.98.