Zero Crossing Switching
Voltage zero-crossing turn-on and current zero-crossing turn-off reduce switching transients. Specified switching inrush is no more than 1.5 times rated current.
FK Series
Intelligent Low Voltage Composite Switch
Intelligent composite switches for low-voltage capacitor-bank switching, with common-compensation and individual-phase versions.
Product Advantages
Voltage zero-crossing turn-on and current zero-crossing turn-off reduce switching transients. Specified switching inrush is no more than 1.5 times rated current.
Optocouplers isolate control input signals from the internal circuit to improve resistance to interference.
Microprocessor monitoring provides power-loss, no-load and phase-loss protection.
The hybrid switching design combines power electronics with a magnetic latching relay and specifies power consumption of no more than 1.5 VA.
DC 12 V control and RS485 versions allow selection to match the compensation controller.
Delta and star versions support common-compensation and individual-phase capacitor arrangements.
The common-compensation switch controls the three phase conductors, so the neutral conductor does not need to pass through the switch.
Standard and circuit-breaker versions support panel mounting or a standard 35 mm DIN rail.
Switching low-voltage capacitor banks in reactive power compensation systems
Delta-connected capacitor banks where the switch controls the three phase conductors
Star-connected capacitor arrangements for individual-phase switching
Compensation cabinets that use a DC 12 V or RS485 controller interface
Low-voltage industrial feeders that switch capacitor steps with limited inrush
Mechanical or electrical rooms that need compact composite-switch capacitor control
Standard or circuit-breaker versions mounted on a panel or a 35 mm DIN rail
Replacing conventional capacitor switching devices where zero-crossing and protection are required
Systems that specify DC 12 V ±10% control or an RS485 version to match the compensation controller
Panel builders integrating FK45A, FK63A or FK80A composite switches into new or existing cabinets
| System | Rated Current | Response Time | Minimum Switching Interval | Power Consumption |
|---|---|---|---|---|
| 220/380 V, 3-phase, 4-wire, 50 Hz | 45 / 63 / 80 A | ≤200 ms | ≥20 s | ≤1.5 VA |
| Control Interface | Switching Capacity | Switching Inrush |
|---|---|---|
| DC 12 V ±10% or RS485 | Common compensation: ≤30 kvar · Individual-phase compensation: ≤10 kvar | ≤1.5 × rated current |
Common Specifications
Common compensation: delta-connected capacitor bank. Individual-phase compensation: star-connected capacitor bank.
Protection functions: power loss, no load and phase loss.
| Version | Overall Dimensions (mm) | Mounting Spacings (mm) | Mounting |
|---|---|---|---|
| Standard | 160 × 91 × 78 | 139 × 32 | Panel / standard 35 mm DIN rail |
| With Circuit Breaker | 215 × 91 × 90 | 194 × 71 × 32 | Panel / standard 35 mm DIN rail |
| Ambient Temperature | Relative Humidity |
|---|---|
| -25°C to +55°C | 20-90% at 40°C |
Common Specifications
For low-voltage power-capacitor switching. When system voltage harmonic content exceeds 5%, select harmonic mitigation according to site conditions.
You can also attach drawings, product photos or test reports, if available.
It combines power-electronic switching with a magnetic-latching relay. The manual specifies turn-on at voltage zero crossing and turn-off at current zero crossing to reduce switching inrush and overvoltage.
The manual lists 45 A, 63 A and 80 A models. It specifies switching capacity of up to 30 kvar for common compensation and up to 10 kvar for individual-phase compensation. Select the switch against the actual capacitor bank and circuit conditions.
Yes, with the corresponding version. The manual identifies the common-compensation type with a delta-connected capacitor and the individual-phase type with a star-connected capacitor. The wiring differs, so specify the required configuration when ordering.
The series manual lists DC 12 V ±10% control or RS485 control. Confirm the interface of the selected model and controller; the two interfaces should not be treated as interchangeable wiring options on one unit.
The specified response time is no more than 200 ms, but the minimum interval between switching operations is 20 seconds. For a faster changing load, evaluate a suitable dynamic switching device instead of relying on response time alone.
Check voltage and current matching, capacitor capacity, wiring and site harmonics. The manual recommends harmonic mitigation measures when system voltage harmonic content exceeds 5%.