APF Harmonic Mitigation for Medium-Frequency Induction Furnace Loads

PROJECT CASE | POWER QUALITY

Optimized active harmonic filtering for a tungsten & molybdenum manufacturing line

INDUSTRY
Tungsten & Molybdenum Processing
APPLICATION
Medium-Frequency Induction Furnace
SOLUTION
Active Power Filter (APF)

Project Background

A tungsten and molybdenum production line uses medium-frequency induction furnaces for metal processing. During operation, the furnaces generated highly distorted current with a broad harmonic spectrum, degrading power quality and interfering with surrounding electrical equipment.

Power Quality Challenge

  • The furnace current waveform was strongly distorted and rich in harmonics.
  • Thyristor commutation produced pronounced voltage notching and fast current changes.
  • An initial APF installation improved the waveform, but oscillation occurred during startup and loaded operation.

Field Diagnosis

On-site waveform analysis confirmed severe current distortion. The diagnostic snapshot below shows phase current THD of approximately 30.5%–31.8%, while the 5th harmonic alone was approximately 23.4%–24.0% at the measured operating point.

30.5–31.8%
Current THD during field diagnosis
23.4–24.0%
5th harmonic share at the captured point
≈40–41 A
5th harmonic current shown in the snapshot

Current THD during diagnosis

5th harmonic spectrum during diagnosis

The site also experienced deep voltage notches during commutation. The previous RC absorption circuit had been removed after repeated failures.


Measurement setup

Voltage waveform

Current waveform

Optimized APF Solution

  • Increase the APF output line-frequency inductance to reduce sensitivity to high-frequency voltage notches.
  • • Optimize output-current fault detection .
  • Refine the shutdown sequence so output current decays before relay disconnection.

Implementation & Results

After hardware and control-logic optimization, the APF operated stably with the induction-furnace load. The project report records stable startup without oscillation, stable operation under load changes, and THDi reduced to within the grid harmonic requirement referenced by the project.

APF installed at the induction-furnace application


APF operating interface during field verification

Load-side operating data during verification

Project Outcomes

Stable Startup
Startup became smooth with no reported oscillation.
Stable Under Load
The APF remained stable and responded rapidly to load changes.
Lower Harmonic Distortion
THDi was reduced to within the grid requirement referenced in the project report.
Improved Reliability
Optimized monitoring and protection reduced nuisance faults and improved operational safety.

CONTACT US

Please share the details you know:

• Product or model
• Application or problem to solve
• Required specifications, such as voltage, frequency or capacity
• Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements