Get A Quote

Home > Products > PFC Components > Detuned Reactor

return

CKSG Series

Detuned Reactor

Detuned Reactor

Series reactors for capacitor banks in low-voltage reactive power compensation systems, with copper and aluminum versions for model selection.

Product Advantages

  • 6 / 7 / 12 / 14% Selection-Table Ratios
  • ≤85 K / ≤95 K Core / Winding Temperature Rise
  • <50 dB Specified Noise
  • ≤1.35 In Overload Capacity

Core Advantages

Harmonic Detuning Choices

Select the reactor ratio to suit the harmonic conditions. Ratios of 6-7% suit 5th-7th harmonics, while 12-14% ratios suit 3rd harmonics.

Switching Inrush Limitation

Series connection with the capacitor bank limits inrush during capacitor switching.

Low Loss Core Material

Low-loss silicon steel sheets reduce magnetic losses in the three-phase core.

Controlled Temperature Rise

At rated current, the specified temperature-rise limits are 85 K for the core and 95 K for the windings.

Insulation for Thermal Duty

Class F or higher insulation supports the stated thermal requirements of capacitor-bank reactor service.

Stable Core Air Gaps

Epoxy-laminated glass-cloth spacers and heat-resistant adhesive stabilize the air gaps. Specified reactor noise is less than 50 dB.

Copper and Aluminum Configurations

Copper and aluminum versions allow conductor-material and cabinet-layout selection using the dimensions specified for each configuration.

Overload Capability

The specified overload-capacity limit is 1.35 times rated current, subject to the selected model and operating conditions.

Product Applications

Detuned banks for 5th–7th harmonics

Capacitor banks that specify a 6–7% reactor ratio at 0.45–0.48 kV capacitor voltage

Detuned banks for 3rd harmonics

Capacitor banks that specify a 12–14% reactor ratio at 0.525 kV capacitor voltage

Low-voltage reactive power compensation

Series reactors used with capacitor banks in low-voltage compensation systems

Switching inrush limitation

Series connection with the capacitor bank to limit inrush during capacitor switching

Industrial plants with harmonic loads

Compensation cabinets where a detuned reactor is selected for the site harmonic conditions

Commercial building compensation

Low-voltage cabinets that need a series reactor with the capacitor bank

Panel-builder compensation assemblies

OEM assemblies that select copper or aluminum CKSG models from the printed tables

Copper or aluminum conductor selection

Layout and conductor-material choice using the dimensions specified for each configuration

Enclosed, ventilated cabinets

Installations that are well ventilated, with cabinet ventilation provided where enclosed

Indoor compensation rooms

Sites without harmful or corrosive gases, flammable or explosive media, severe vibration or jolting, or rain or snow exposure

Electrical Ratings

Rated Capacitor Voltage Reactor Ratios Degree of Protection
AC 0.45 / 0.48 / 0.525 kV 4.5 / 5.6 / 6 / 7 / 12 / 13 / 14% IP00

Selection Guidance

Reactor Ratio Capacitor Voltage Selection Harmonic Application
6-7% 0.45-0.48 kV 5th-7th harmonics
12-14% 0.525 kV 3rd harmonics

Common Specifications

Reactor reactive power = compatible capacitor capacity × reactor ratio. Other voltages are available by special request.

Thermal and Insulation Ratings

Core Temperature Rise Winding Temperature Rise Withstand Voltage Noise Insulation Class Overload Capacity
≤85 K ≤95 K 3000 V/min <50 dB F or higher ≤1.35 × In

Common Specifications

Temperature-rise limits apply at rated current.

Operating Conditions

Ambient Temperature Altitude Installation
-25°C to +40°C ≤2000 m Well ventilated; provide cabinet ventilation where enclosed

Common Specifications

No harmful or corrosive gases, flammable / explosive media, severe vibration or jolting, or rain / snow exposure.

Standards: GB/T 19212.1-2016; GB/T 1094.6.

Copper · 0.45 kV / 6% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.3/0.45-6% 0.3 5 6% 180×85×180 150×60 φ9×17 L
CKSG-0.6/0.45-6% 0.6 10 6% 180×95×180 150×70 φ9×17 L
CKSG-0.9/0.45-6% 0.9 15 6% 180×150×165 150×80 φ9×17 II
CKSG-1.2/0.45-6% 1.2 20 6% 180×160×185 150×85 φ9×17 II
CKSG-1.5/0.45-6% 1.5 25 6% 180×170×185 150×90 φ9×17 II
CKSG-1.8/0.45-6% 1.8 30 6% 240×190×205 190×100 φ9×18 II
CKSG-2.1/0.45-6% 2.1 35 6% 240×195×205 190×105 φ9×18 II
CKSG-2.4/0.45-6% 2.4 40 6% 240×200×230 190×110 φ9×18 II
CKSG-2.7/0.45-6% 2.7 45 6% 240×200×230 190×110 φ9×18 II
CKSG-3.0/0.45-6% 3 50 6% 240×205×230 190×115 φ9×18 II
CKSG-3.6/0.45-6% 3.6 60 6% 250×210×250 190×115 φ9×18 II
CKSG-4.2/0.45-6% 4.2 70 6% 270×225×255 220×125 φ9×18 II

Copper · 0.45 kV / 7% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.35/0.45-7% 0.35 5 7% 180×85×180 150×60 φ9×17 L
CKSG-0.7/0.45-7% 0.7 10 7% 180×105×180 150×75 φ9×17 L
CKSG-1.05/0.45-7% 1.05 15 7% 180×155×165 150×80 φ9×17 II
CKSG-1.4/0.45-7% 1.4 20 7% 180×170×180 150×95 φ9×17 II
CKSG-1.75/0.45-7% 1.75 25 7% 240×170×205 190×100 φ9×18 II
CKSG-2.1/0.45-7% 2.1 30 7% 240×180×205 190×105 φ9×18 II
CKSG-2.45/0.45-7% 2.45 35 7% 240×185×235 190×105 φ9×18 II
CKSG-2.8/0.45-7% 2.8 40 7% 240×190×235 190×110 φ9×18 II
CKSG-3.15/0.45-7% 3.15 45 7% 250×195×255 190×115 φ9×18 II
CKSG-3.5/0.45-7% 3.5 50 7% 250×195×255 190×115 φ9×18 II
CKSG-4.2/0.45-7% 4.2 60 7% 270×210×255 220×125 φ9×18 II
CKSG-4.9/0.45-7% 4.9 70 7% 270×210×290 210×115 φ9×18 II

Copper · 0.48 kV / 7% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.35/0.48-7% 0.35 5 7% 180×85×180 150×60 φ9×17 L
CKSG-0.7/0.48-7% 0.7 10 7% 180×105×180 150×75 φ9×17 L
CKSG-1.05/0.48-7% 1.05 15 7% 180×145×180 150×75 φ9×17 II
CKSG-1.4/0.48-7% 1.4 20 7% 180×170×180 150×95 φ9×17 II
CKSG-1.75/0.48-7% 1.75 25 7% 240×170×205 190×100 φ9×18 II
CKSG-2.1/0.48-7% 2.1 30 7% 240×180×205 190×105 φ9×18 II
CKSG-2.45/0.48-7% 2.45 35 7% 240×185×235 190×105 φ9×18 II
CKSG-2.8/0.48-7% 2.8 40 7% 240×190×235 190×110 φ9×18 II
CKSG-3.15/0.48-7% 3.15 45 7% 240×195×235 190×115 φ9×18 II
CKSG-3.5/0.48-7% 3.5 50 7% 250×195×255 190×115 φ9×18 II
CKSG-4.2/0.48-7% 4.2 60 7% 270×210×255 220×125 φ9×18 II
CKSG-4.9/0.48-7% 4.9 70 7% 270×210×290 210×115 φ9×18 II

Copper · 0.525 kV / 12% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.6/0.525-12% 0.6 5 12% 180×90×180 150×65 φ9×17 II
CKSG-1.2/0.525-12% 1.2 10 12% 200×115×180 170×80 φ9×17 II
CKSG-1.8/0.525-12% 1.8 15 12% 200×165×200 170×90 φ9×17 II
CKSG-2.4/0.525-12% 2.4 20 12% 200×165×200 170×90 φ9×17 II
CKSG-3.0/0.525-12% 3 25 12% 240×170×235 200×90 φ9×18 II
CKSG-3.6/0.525-12% 3.6 30 12% 240×185×255 200×100 φ9×18 II
CKSG-4.2/0.525-12% 4.2 35 12% 250×200×255 200×100 φ9×18 II
CKSG-4.8/0.525-12% 4.8 40 12% 250×200×305 210×110 φ9×18 II
CKSG-5.4/0.525-12% 5.4 45 12% 300×200×285 210×120 φ9×18 II
CKSG-6.0/0.525-12% 6 50 12% 300×200×285 240×105 φ10×21 II
CKSG-7.2/0.525-12% 7.2 60 12% 300×210×285 240×115 φ10×21 II
CKSG-8.4/0.525-12% 8.4 70 12% 300×230×285 240×135 φ10×21 II

Copper · 0.525 kV / 14% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.7/0.525-14% 0.7 5 14% 180×100×180 150×70 φ9×17 L
CKSG-1.4/0.525-14% 1.4 10 14% 180×120×200 150×95 φ9×17 L
CKSG-2.1/0.525-14% 2.1 15 14% 240×200×205 190×110 φ9×18 II
CKSG-2.8/0.525-14% 2.8 20 14% 240×195×235 190×105 φ9×18 II
CKSG-3.5/0.525-14% 3.5 25 14% 240×215×235 190×125 φ9×18 II
CKSG-4.2/0.525-14% 4.2 30 14% 270×210×255 220×120 φ9×18 II
CKSG-4.9/0.525-14% 4.9 35 14% 270×210×290 210×115 φ9×18 II
CKSG-5.6/0.525-14% 5.6 40 14% 270×210×290 210×115 φ9×18 II
CKSG-6.3/0.525-14% 6.3 45 14% 300×220×285 240×125 φ10×21 II
CKSG-7.0/0.525-14% 7 50 14% 300×230×285 240×135 φ10×21 II
CKSG-8.4/0.525-14% 8.4 60 14% 300×250×285 240×155 φ10×21 II
CKSG-9.8/0.525-14% 9.8 70 14% 300×260×285 240×165 φ10×21 II

Common Specifications

Overall dimension tolerance: ±10 mm. Mounting dimension tolerance: ±5 mm.

Aluminum · 0.45 kV / 6% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.3/0.45-6% 0.3 5 6% 180×85×180 150×60 φ9×17 L
CKSG-0.6/0.45-6% 0.6 10 6% 180×85×180 150×60 φ9×17 L
CKSG-0.9/0.45-6% 0.9 15 6% 180×160×165 150×75 φ9×17 II
CKSG-1.2/0.45-6% 1.2 20 6% 180×160×185 150×75 φ9×17 II
CKSG-1.5/0.45-6% 1.5 25 6% 200×170×185 170×85 φ9×17 II
CKSG-1.8/0.45-6% 1.8 30 6% 200×175×205 170×90 φ9×17 II
CKSG-2.1/0.45-6% 2.1 35 6% 200×175×205 170×90 φ9×17 II
CKSG-2.4/0.45-6% 2.4 40 6% 200×185×210 170×95 φ9×17 II
CKSG-2.7/0.45-6% 2.7 45 6% 240×190×235 190×95 φ9×18 II
CKSG-3.0/0.45-6% 3 50 6% 240×190×235 190×95 φ9×18 II
CKSG-3.6/0.45-6% 3.6 60 6% 240×220×235 190×105 φ9×18 II
CKSG-4.2/0.45-6% 4.2 70 6% 240×225×235 190×115 φ9×18 II

Aluminum · 0.45 kV / 7% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.35/0.45-7% 0.35 5 7% 180×85×180 150×60 φ9×17 L
CKSG-0.7/0.45-7% 0.7 10 7% 180×105×180 150×70 φ9×17 L
CKSG-1.05/0.45-7% 1.05 15 7% 180×155×165 150×80 φ9×17 II
CKSG-1.4/0.45-7% 1.4 20 7% 200×160×180 170×85 φ9×17 II
CKSG-1.75/0.45-7% 1.75 25 7% 200×180×205 170×95 φ9×17 II
CKSG-2.1/0.45-7% 2.1 30 7% 200×180×205 170×95 φ9×17 II
CKSG-2.45/0.45-7% 2.45 35 7% 240×185×235 200×90 φ9×18 II
CKSG-2.8/0.45-7% 2.8 40 7% 240×185×235 200×95 φ9×18 II
CKSG-3.15/0.45-7% 3.15 45 7% 240×190×235 200×105 φ9×18 II
CKSG-3.5/0.45-7% 3.5 50 7% 240×200×235 200×105 φ9×18 II
CKSG-4.2/0.45-7% 4.2 60 7% 240×210×235 200×115 φ9×18 II
CKSG-4.9/0.45-7% 4.9 70 7% 250×210×255 210×115 φ9×18 II

Aluminum · 0.48 kV / 7% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.35/0.48-7% 0.35 5 7% 180×95×180 150×60 φ9×17 L
CKSG-0.7/0.48-7% 0.7 10 7% 180×105×180 150×70 φ9×17 L
CKSG-1.05/0.48-7% 1.05 15 7% 180×155×165 150×80 φ9×17 II
CKSG-1.4/0.48-7% 1.4 20 7% 200×165×180 170×90 φ9×17 II
CKSG-1.75/0.48-7% 1.75 25 7% 200×180×205 170×95 φ9×17 II
CKSG-2.1/0.48-7% 2.1 30 7% 200×180×205 170×95 φ9×17 II
CKSG-2.45/0.48-7% 2.45 35 7% 240×180×235 200×90 φ9×18 II
CKSG-2.8/0.48-7% 2.8 40 7% 240×185×235 200×95 φ9×18 II
CKSG-3.15/0.48-7% 3.15 45 7% 240×190×235 200×100 φ9×18 II
CKSG-3.5/0.48-7% 3.5 50 7% 240×200×235 200×105 φ9×18 II
CKSG-4.2/0.48-7% 4.2 60 7% 240×220×235 200×125 φ9×18 II
CKSG-4.9/0.48-7% 4.9 70 7% 250×210×255 210×110 φ9×18 II

Aluminum · 0.525 kV / 12% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.6/0.525-12% 0.6 5 12% 180×90×180 150×65 φ9×17 II
CKSG-1.2/0.525-12% 1.2 10 12% 200×115×180 170×80 φ9×17 II
CKSG-1.8/0.525-12% 1.8 15 12% 200×165×200 170×90 φ9×17 II
CKSG-2.4/0.525-12% 2.4 20 12% 200×165×200 170×90 φ9×17 II
CKSG-3.0/0.525-12% 3 25 12% 240×170×235 200×90 φ9×18 II
CKSG-3.6/0.525-12% 3.6 30 12% 240×185×255 200×100 φ9×18 II
CKSG-4.2/0.525-12% 4.2 35 12% 250×200×255 200×100 φ9×18 II
CKSG-4.8/0.525-12% 4.8 40 12% 250×200×305 210×110 φ9×18 II
CKSG-5.4/0.525-12% 5.4 45 12% 300×200×285 210×120 φ9×18 II
CKSG-6.0/0.525-12% 6 50 12% 300×200×285 240×105 φ10×21 II
CKSG-7.2/0.525-12% 7.2 60 12% 300×210×285 240×115 φ10×21 II
CKSG-8.4/0.525-12% 8.4 70 12% 300×230×285 240×135 φ10×21 II

Aluminum · 0.525 kV / 14% Reactance Ratio

Model Reactor (kvar) Capacitor (kvar) Ratio Overall L × W × H (mm) Mounting A × B (mm) Holes a × b (mm) Outline
CKSG-0.7/0.525-14% 0.7 5 14% 180×100×200 150×65 φ9×17 L
CKSG-1.4/0.525-14% 1.4 10 14% 200×115×200 170×80 φ9×17 L
CKSG-2.1/0.525-14% 2.1 15 14% 200×175×205 170×95 φ9×17 II
CKSG-2.8/0.525-14% 2.8 20 14% 240×185×235 200×95 φ9×18 II
CKSG-3.5/0.525-14% 3.5 25 14% 240×195×235 200×105 φ9×18 II
CKSG-4.2/0.525-14% 4.2 30 14% 240×200×255 200×105 φ9×18 II
CKSG-4.9/0.525-14% 4.9 35 14% 240×220×235 200×125 φ9×18 II
CKSG-5.6/0.525-14% 5.6 40 14% 250×210×300 210×115 φ9×18 II
CKSG-6.3/0.525-14% 6.3 45 14% 250×210×300 210×115 φ9×18 II
CKSG-7.0/0.525-14% 7 50 14% 300×210×285 240×120 φ10×21 II
CKSG-8.4/0.525-14% 8.4 60 14% 300×230×285 240×130 φ10×21 II
CKSG-9.8/0.525-14% 9.8 70 14% 300×240×285 240×140 φ10×21 II

Common Specifications

Overall dimension tolerance: ±10 mm. Mounting dimension tolerance: ±5 mm.

Please Share the Details You Know:

  • Product or model
  • Application or problem to solve
  • Required specifications, such as voltage, frequency or capacity
  • Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements

FAQ

Why is a reactor installed in series with a compensation capacitor?

A correctly selected reactor and capacitor form a detuned compensation branch. The reactor helps limit switching inrush and reduce the risk of harmonic amplification or resonance associated with connecting capacitor banks. It is not a standalone active harmonic filter.

How should I choose the reactor ratio?

Start with the site’s harmonic measurements and the capacitor branch design. The manual gives 6%–7% as a selection guide for systems with 5th–7th harmonics and 12%–14% for 3rd-harmonic conditions. The final ratio needs project-specific verification.

Can I select a reactor using capacitor kvar alone?

No. The order information also calls for the reactor ratio, capacitor rated voltage and wiring configuration. Provide the capacitor capacity or the reactor’s rated capacity so the pair can be matched.

What voltage options does the manual list?

It lists AC 0.45 kV, 0.48 kV and 0.525 kV versions, with other voltages available by special request. The manual associates 0.45–0.48 kV with 6%–7% designs and 0.525 kV with 12%–14% designs.

Can the reactor be installed inside a compensation cabinet?

Yes, provided the cabinet has adequate ventilation. The manual calls for ventilation equipment when installed inside a cabinet and specifies an ambient temperature of −25 °C to +40 °C and altitude up to 2,000 m.

What should I send to receive a suitable quotation?

Send the capacitor voltage and kvar, system voltage, site harmonic data, required reactor ratio if already determined, wiring configuration, quantity, and any cabinet space or mounting limits.