Harmonic Detuning Choices
Select the reactor ratio to suit the harmonic conditions. Ratios of 6-7% suit 5th-7th harmonics, while 12-14% ratios suit 3rd harmonics.
CKSG Series
Detuned Reactor
Series reactors for capacitor banks in low-voltage reactive power compensation systems, with copper and aluminum versions for model selection.
Product Advantages
Select the reactor ratio to suit the harmonic conditions. Ratios of 6-7% suit 5th-7th harmonics, while 12-14% ratios suit 3rd harmonics.
Series connection with the capacitor bank limits inrush during capacitor switching.
Low-loss silicon steel sheets reduce magnetic losses in the three-phase core.
At rated current, the specified temperature-rise limits are 85 K for the core and 95 K for the windings.
Class F or higher insulation supports the stated thermal requirements of capacitor-bank reactor service.
Epoxy-laminated glass-cloth spacers and heat-resistant adhesive stabilize the air gaps. Specified reactor noise is less than 50 dB.
Copper and aluminum versions allow conductor-material and cabinet-layout selection using the dimensions specified for each configuration.
The specified overload-capacity limit is 1.35 times rated current, subject to the selected model and operating conditions.
Capacitor banks that specify a 6–7% reactor ratio at 0.45–0.48 kV capacitor voltage
Capacitor banks that specify a 12–14% reactor ratio at 0.525 kV capacitor voltage
Series reactors used with capacitor banks in low-voltage compensation systems
Series connection with the capacitor bank to limit inrush during capacitor switching
Compensation cabinets where a detuned reactor is selected for the site harmonic conditions
Low-voltage cabinets that need a series reactor with the capacitor bank
OEM assemblies that select copper or aluminum CKSG models from the printed tables
Layout and conductor-material choice using the dimensions specified for each configuration
Installations that are well ventilated, with cabinet ventilation provided where enclosed
Sites without harmful or corrosive gases, flammable or explosive media, severe vibration or jolting, or rain or snow exposure
| Rated Capacitor Voltage | Reactor Ratios | Degree of Protection |
|---|---|---|
| AC 0.45 / 0.48 / 0.525 kV | 4.5 / 5.6 / 6 / 7 / 12 / 13 / 14% | IP00 |
| Reactor Ratio | Capacitor Voltage Selection | Harmonic Application |
|---|---|---|
| 6-7% | 0.45-0.48 kV | 5th-7th harmonics |
| 12-14% | 0.525 kV | 3rd harmonics |
Common Specifications
Reactor reactive power = compatible capacitor capacity × reactor ratio. Other voltages are available by special request.
| Core Temperature Rise | Winding Temperature Rise | Withstand Voltage | Noise | Insulation Class | Overload Capacity |
|---|---|---|---|---|---|
| ≤85 K | ≤95 K | 3000 V/min | <50 dB | F or higher | ≤1.35 × In |
Common Specifications
Temperature-rise limits apply at rated current.
| Ambient Temperature | Altitude | Installation |
|---|---|---|
| -25°C to +40°C | ≤2000 m | Well ventilated; provide cabinet ventilation where enclosed |
Common Specifications
No harmful or corrosive gases, flammable / explosive media, severe vibration or jolting, or rain / snow exposure.
Standards: GB/T 19212.1-2016; GB/T 1094.6.
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.3/0.45-6% | 0.3 | 5 | 6% | 180×85×180 | 150×60 | φ9×17 | L |
| CKSG-0.6/0.45-6% | 0.6 | 10 | 6% | 180×95×180 | 150×70 | φ9×17 | L |
| CKSG-0.9/0.45-6% | 0.9 | 15 | 6% | 180×150×165 | 150×80 | φ9×17 | II |
| CKSG-1.2/0.45-6% | 1.2 | 20 | 6% | 180×160×185 | 150×85 | φ9×17 | II |
| CKSG-1.5/0.45-6% | 1.5 | 25 | 6% | 180×170×185 | 150×90 | φ9×17 | II |
| CKSG-1.8/0.45-6% | 1.8 | 30 | 6% | 240×190×205 | 190×100 | φ9×18 | II |
| CKSG-2.1/0.45-6% | 2.1 | 35 | 6% | 240×195×205 | 190×105 | φ9×18 | II |
| CKSG-2.4/0.45-6% | 2.4 | 40 | 6% | 240×200×230 | 190×110 | φ9×18 | II |
| CKSG-2.7/0.45-6% | 2.7 | 45 | 6% | 240×200×230 | 190×110 | φ9×18 | II |
| CKSG-3.0/0.45-6% | 3 | 50 | 6% | 240×205×230 | 190×115 | φ9×18 | II |
| CKSG-3.6/0.45-6% | 3.6 | 60 | 6% | 250×210×250 | 190×115 | φ9×18 | II |
| CKSG-4.2/0.45-6% | 4.2 | 70 | 6% | 270×225×255 | 220×125 | φ9×18 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.35/0.45-7% | 0.35 | 5 | 7% | 180×85×180 | 150×60 | φ9×17 | L |
| CKSG-0.7/0.45-7% | 0.7 | 10 | 7% | 180×105×180 | 150×75 | φ9×17 | L |
| CKSG-1.05/0.45-7% | 1.05 | 15 | 7% | 180×155×165 | 150×80 | φ9×17 | II |
| CKSG-1.4/0.45-7% | 1.4 | 20 | 7% | 180×170×180 | 150×95 | φ9×17 | II |
| CKSG-1.75/0.45-7% | 1.75 | 25 | 7% | 240×170×205 | 190×100 | φ9×18 | II |
| CKSG-2.1/0.45-7% | 2.1 | 30 | 7% | 240×180×205 | 190×105 | φ9×18 | II |
| CKSG-2.45/0.45-7% | 2.45 | 35 | 7% | 240×185×235 | 190×105 | φ9×18 | II |
| CKSG-2.8/0.45-7% | 2.8 | 40 | 7% | 240×190×235 | 190×110 | φ9×18 | II |
| CKSG-3.15/0.45-7% | 3.15 | 45 | 7% | 250×195×255 | 190×115 | φ9×18 | II |
| CKSG-3.5/0.45-7% | 3.5 | 50 | 7% | 250×195×255 | 190×115 | φ9×18 | II |
| CKSG-4.2/0.45-7% | 4.2 | 60 | 7% | 270×210×255 | 220×125 | φ9×18 | II |
| CKSG-4.9/0.45-7% | 4.9 | 70 | 7% | 270×210×290 | 210×115 | φ9×18 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.35/0.48-7% | 0.35 | 5 | 7% | 180×85×180 | 150×60 | φ9×17 | L |
| CKSG-0.7/0.48-7% | 0.7 | 10 | 7% | 180×105×180 | 150×75 | φ9×17 | L |
| CKSG-1.05/0.48-7% | 1.05 | 15 | 7% | 180×145×180 | 150×75 | φ9×17 | II |
| CKSG-1.4/0.48-7% | 1.4 | 20 | 7% | 180×170×180 | 150×95 | φ9×17 | II |
| CKSG-1.75/0.48-7% | 1.75 | 25 | 7% | 240×170×205 | 190×100 | φ9×18 | II |
| CKSG-2.1/0.48-7% | 2.1 | 30 | 7% | 240×180×205 | 190×105 | φ9×18 | II |
| CKSG-2.45/0.48-7% | 2.45 | 35 | 7% | 240×185×235 | 190×105 | φ9×18 | II |
| CKSG-2.8/0.48-7% | 2.8 | 40 | 7% | 240×190×235 | 190×110 | φ9×18 | II |
| CKSG-3.15/0.48-7% | 3.15 | 45 | 7% | 240×195×235 | 190×115 | φ9×18 | II |
| CKSG-3.5/0.48-7% | 3.5 | 50 | 7% | 250×195×255 | 190×115 | φ9×18 | II |
| CKSG-4.2/0.48-7% | 4.2 | 60 | 7% | 270×210×255 | 220×125 | φ9×18 | II |
| CKSG-4.9/0.48-7% | 4.9 | 70 | 7% | 270×210×290 | 210×115 | φ9×18 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.6/0.525-12% | 0.6 | 5 | 12% | 180×90×180 | 150×65 | φ9×17 | II |
| CKSG-1.2/0.525-12% | 1.2 | 10 | 12% | 200×115×180 | 170×80 | φ9×17 | II |
| CKSG-1.8/0.525-12% | 1.8 | 15 | 12% | 200×165×200 | 170×90 | φ9×17 | II |
| CKSG-2.4/0.525-12% | 2.4 | 20 | 12% | 200×165×200 | 170×90 | φ9×17 | II |
| CKSG-3.0/0.525-12% | 3 | 25 | 12% | 240×170×235 | 200×90 | φ9×18 | II |
| CKSG-3.6/0.525-12% | 3.6 | 30 | 12% | 240×185×255 | 200×100 | φ9×18 | II |
| CKSG-4.2/0.525-12% | 4.2 | 35 | 12% | 250×200×255 | 200×100 | φ9×18 | II |
| CKSG-4.8/0.525-12% | 4.8 | 40 | 12% | 250×200×305 | 210×110 | φ9×18 | II |
| CKSG-5.4/0.525-12% | 5.4 | 45 | 12% | 300×200×285 | 210×120 | φ9×18 | II |
| CKSG-6.0/0.525-12% | 6 | 50 | 12% | 300×200×285 | 240×105 | φ10×21 | II |
| CKSG-7.2/0.525-12% | 7.2 | 60 | 12% | 300×210×285 | 240×115 | φ10×21 | II |
| CKSG-8.4/0.525-12% | 8.4 | 70 | 12% | 300×230×285 | 240×135 | φ10×21 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.7/0.525-14% | 0.7 | 5 | 14% | 180×100×180 | 150×70 | φ9×17 | L |
| CKSG-1.4/0.525-14% | 1.4 | 10 | 14% | 180×120×200 | 150×95 | φ9×17 | L |
| CKSG-2.1/0.525-14% | 2.1 | 15 | 14% | 240×200×205 | 190×110 | φ9×18 | II |
| CKSG-2.8/0.525-14% | 2.8 | 20 | 14% | 240×195×235 | 190×105 | φ9×18 | II |
| CKSG-3.5/0.525-14% | 3.5 | 25 | 14% | 240×215×235 | 190×125 | φ9×18 | II |
| CKSG-4.2/0.525-14% | 4.2 | 30 | 14% | 270×210×255 | 220×120 | φ9×18 | II |
| CKSG-4.9/0.525-14% | 4.9 | 35 | 14% | 270×210×290 | 210×115 | φ9×18 | II |
| CKSG-5.6/0.525-14% | 5.6 | 40 | 14% | 270×210×290 | 210×115 | φ9×18 | II |
| CKSG-6.3/0.525-14% | 6.3 | 45 | 14% | 300×220×285 | 240×125 | φ10×21 | II |
| CKSG-7.0/0.525-14% | 7 | 50 | 14% | 300×230×285 | 240×135 | φ10×21 | II |
| CKSG-8.4/0.525-14% | 8.4 | 60 | 14% | 300×250×285 | 240×155 | φ10×21 | II |
| CKSG-9.8/0.525-14% | 9.8 | 70 | 14% | 300×260×285 | 240×165 | φ10×21 | II |
Common Specifications
Overall dimension tolerance: ±10 mm. Mounting dimension tolerance: ±5 mm.
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.3/0.45-6% | 0.3 | 5 | 6% | 180×85×180 | 150×60 | φ9×17 | L |
| CKSG-0.6/0.45-6% | 0.6 | 10 | 6% | 180×85×180 | 150×60 | φ9×17 | L |
| CKSG-0.9/0.45-6% | 0.9 | 15 | 6% | 180×160×165 | 150×75 | φ9×17 | II |
| CKSG-1.2/0.45-6% | 1.2 | 20 | 6% | 180×160×185 | 150×75 | φ9×17 | II |
| CKSG-1.5/0.45-6% | 1.5 | 25 | 6% | 200×170×185 | 170×85 | φ9×17 | II |
| CKSG-1.8/0.45-6% | 1.8 | 30 | 6% | 200×175×205 | 170×90 | φ9×17 | II |
| CKSG-2.1/0.45-6% | 2.1 | 35 | 6% | 200×175×205 | 170×90 | φ9×17 | II |
| CKSG-2.4/0.45-6% | 2.4 | 40 | 6% | 200×185×210 | 170×95 | φ9×17 | II |
| CKSG-2.7/0.45-6% | 2.7 | 45 | 6% | 240×190×235 | 190×95 | φ9×18 | II |
| CKSG-3.0/0.45-6% | 3 | 50 | 6% | 240×190×235 | 190×95 | φ9×18 | II |
| CKSG-3.6/0.45-6% | 3.6 | 60 | 6% | 240×220×235 | 190×105 | φ9×18 | II |
| CKSG-4.2/0.45-6% | 4.2 | 70 | 6% | 240×225×235 | 190×115 | φ9×18 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.35/0.45-7% | 0.35 | 5 | 7% | 180×85×180 | 150×60 | φ9×17 | L |
| CKSG-0.7/0.45-7% | 0.7 | 10 | 7% | 180×105×180 | 150×70 | φ9×17 | L |
| CKSG-1.05/0.45-7% | 1.05 | 15 | 7% | 180×155×165 | 150×80 | φ9×17 | II |
| CKSG-1.4/0.45-7% | 1.4 | 20 | 7% | 200×160×180 | 170×85 | φ9×17 | II |
| CKSG-1.75/0.45-7% | 1.75 | 25 | 7% | 200×180×205 | 170×95 | φ9×17 | II |
| CKSG-2.1/0.45-7% | 2.1 | 30 | 7% | 200×180×205 | 170×95 | φ9×17 | II |
| CKSG-2.45/0.45-7% | 2.45 | 35 | 7% | 240×185×235 | 200×90 | φ9×18 | II |
| CKSG-2.8/0.45-7% | 2.8 | 40 | 7% | 240×185×235 | 200×95 | φ9×18 | II |
| CKSG-3.15/0.45-7% | 3.15 | 45 | 7% | 240×190×235 | 200×105 | φ9×18 | II |
| CKSG-3.5/0.45-7% | 3.5 | 50 | 7% | 240×200×235 | 200×105 | φ9×18 | II |
| CKSG-4.2/0.45-7% | 4.2 | 60 | 7% | 240×210×235 | 200×115 | φ9×18 | II |
| CKSG-4.9/0.45-7% | 4.9 | 70 | 7% | 250×210×255 | 210×115 | φ9×18 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.35/0.48-7% | 0.35 | 5 | 7% | 180×95×180 | 150×60 | φ9×17 | L |
| CKSG-0.7/0.48-7% | 0.7 | 10 | 7% | 180×105×180 | 150×70 | φ9×17 | L |
| CKSG-1.05/0.48-7% | 1.05 | 15 | 7% | 180×155×165 | 150×80 | φ9×17 | II |
| CKSG-1.4/0.48-7% | 1.4 | 20 | 7% | 200×165×180 | 170×90 | φ9×17 | II |
| CKSG-1.75/0.48-7% | 1.75 | 25 | 7% | 200×180×205 | 170×95 | φ9×17 | II |
| CKSG-2.1/0.48-7% | 2.1 | 30 | 7% | 200×180×205 | 170×95 | φ9×17 | II |
| CKSG-2.45/0.48-7% | 2.45 | 35 | 7% | 240×180×235 | 200×90 | φ9×18 | II |
| CKSG-2.8/0.48-7% | 2.8 | 40 | 7% | 240×185×235 | 200×95 | φ9×18 | II |
| CKSG-3.15/0.48-7% | 3.15 | 45 | 7% | 240×190×235 | 200×100 | φ9×18 | II |
| CKSG-3.5/0.48-7% | 3.5 | 50 | 7% | 240×200×235 | 200×105 | φ9×18 | II |
| CKSG-4.2/0.48-7% | 4.2 | 60 | 7% | 240×220×235 | 200×125 | φ9×18 | II |
| CKSG-4.9/0.48-7% | 4.9 | 70 | 7% | 250×210×255 | 210×110 | φ9×18 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.6/0.525-12% | 0.6 | 5 | 12% | 180×90×180 | 150×65 | φ9×17 | II |
| CKSG-1.2/0.525-12% | 1.2 | 10 | 12% | 200×115×180 | 170×80 | φ9×17 | II |
| CKSG-1.8/0.525-12% | 1.8 | 15 | 12% | 200×165×200 | 170×90 | φ9×17 | II |
| CKSG-2.4/0.525-12% | 2.4 | 20 | 12% | 200×165×200 | 170×90 | φ9×17 | II |
| CKSG-3.0/0.525-12% | 3 | 25 | 12% | 240×170×235 | 200×90 | φ9×18 | II |
| CKSG-3.6/0.525-12% | 3.6 | 30 | 12% | 240×185×255 | 200×100 | φ9×18 | II |
| CKSG-4.2/0.525-12% | 4.2 | 35 | 12% | 250×200×255 | 200×100 | φ9×18 | II |
| CKSG-4.8/0.525-12% | 4.8 | 40 | 12% | 250×200×305 | 210×110 | φ9×18 | II |
| CKSG-5.4/0.525-12% | 5.4 | 45 | 12% | 300×200×285 | 210×120 | φ9×18 | II |
| CKSG-6.0/0.525-12% | 6 | 50 | 12% | 300×200×285 | 240×105 | φ10×21 | II |
| CKSG-7.2/0.525-12% | 7.2 | 60 | 12% | 300×210×285 | 240×115 | φ10×21 | II |
| CKSG-8.4/0.525-12% | 8.4 | 70 | 12% | 300×230×285 | 240×135 | φ10×21 | II |
| Model | Reactor (kvar) | Capacitor (kvar) | Ratio | Overall L × W × H (mm) | Mounting A × B (mm) | Holes a × b (mm) | Outline |
|---|---|---|---|---|---|---|---|
| CKSG-0.7/0.525-14% | 0.7 | 5 | 14% | 180×100×200 | 150×65 | φ9×17 | L |
| CKSG-1.4/0.525-14% | 1.4 | 10 | 14% | 200×115×200 | 170×80 | φ9×17 | L |
| CKSG-2.1/0.525-14% | 2.1 | 15 | 14% | 200×175×205 | 170×95 | φ9×17 | II |
| CKSG-2.8/0.525-14% | 2.8 | 20 | 14% | 240×185×235 | 200×95 | φ9×18 | II |
| CKSG-3.5/0.525-14% | 3.5 | 25 | 14% | 240×195×235 | 200×105 | φ9×18 | II |
| CKSG-4.2/0.525-14% | 4.2 | 30 | 14% | 240×200×255 | 200×105 | φ9×18 | II |
| CKSG-4.9/0.525-14% | 4.9 | 35 | 14% | 240×220×235 | 200×125 | φ9×18 | II |
| CKSG-5.6/0.525-14% | 5.6 | 40 | 14% | 250×210×300 | 210×115 | φ9×18 | II |
| CKSG-6.3/0.525-14% | 6.3 | 45 | 14% | 250×210×300 | 210×115 | φ9×18 | II |
| CKSG-7.0/0.525-14% | 7 | 50 | 14% | 300×210×285 | 240×120 | φ10×21 | II |
| CKSG-8.4/0.525-14% | 8.4 | 60 | 14% | 300×230×285 | 240×130 | φ10×21 | II |
| CKSG-9.8/0.525-14% | 9.8 | 70 | 14% | 300×240×285 | 240×140 | φ10×21 | II |
Common Specifications
Overall dimension tolerance: ±10 mm. Mounting dimension tolerance: ±5 mm.
You can also attach drawings, product photos or test reports, if available.
A correctly selected reactor and capacitor form a detuned compensation branch. The reactor helps limit switching inrush and reduce the risk of harmonic amplification or resonance associated with connecting capacitor banks. It is not a standalone active harmonic filter.
Start with the site’s harmonic measurements and the capacitor branch design. The manual gives 6%–7% as a selection guide for systems with 5th–7th harmonics and 12%–14% for 3rd-harmonic conditions. The final ratio needs project-specific verification.
No. The order information also calls for the reactor ratio, capacitor rated voltage and wiring configuration. Provide the capacitor capacity or the reactor’s rated capacity so the pair can be matched.
It lists AC 0.45 kV, 0.48 kV and 0.525 kV versions, with other voltages available by special request. The manual associates 0.45–0.48 kV with 6%–7% designs and 0.525 kV with 12%–14% designs.
Yes, provided the cabinet has adequate ventilation. The manual calls for ventilation equipment when installed inside a cabinet and specifies an ambient temperature of −25 °C to +40 °C and altitude up to 2,000 m.
Send the capacitor voltage and kvar, system voltage, site harmonic data, required reactor ratio if already determined, wiring configuration, quantity, and any cabinet space or mounting limits.