EV Charging Station – Low Power Factor from Capacitive Reactive Power

PROJECT CASE | EV CHARGING STATION

SVG compensation for 21 DC chargers in daytime standby — power factor restored from 0.1–0.2 (capacitive) to 0.99 (inductive), annual saving RMB 76,000.

INDUSTRY
EV Charging Infrastructure
INSTALLED CHARGERS
21 DC chargers
OPERATING CONDITION
Daytime standby

1. Project Background

The site has 21 DC chargers. During daytime, the chargers are mainly in standby. Capacitive reactive power is present, resulting in a low system power factor. The existing capacitor bank could not meet this reactive power compensation requirement.

Charging station site.

2. Measured Condition

Measurements were taken on the low-voltage sides of a 2500 kVA transformer and a 2000 kVA transformer while the chargers were in standby.

Point Transformer Total Capacitive Reactive Power Power Factor
P01 2500 kVA 50.26 kvar 0.1–0.2, capacitive
P06 2000 kVA 38.16 kvar 0.1–0.2, capacitive

3. Measurement Evidence

P01 — 2500 kVA transformer P06 — 2000 kVA transformer
Power Power Factor

Source evidence: standby measurements on the low-voltage sides of both transformers.

4. SVG Compensation Solution

One 100 kvar SVG module was recommended for each transformer section.

  • The existing capacitor cabinet was emptied and its structure adjusted to install the 100 kvar SVG module.
  • Current transformers with accuracy class 0.2 or higher were specified: 4000:5 for the 2500 kVA transformer section and 3000:5 for the 2000 kVA transformer section.
  • Based on the reactive power measured while the chargers were in standby, the SVG constant-reactive-power function was used to set a fixed reactive current output.
  • If system reactive power varies significantly, the compensation effect may decrease.

5. Installation Diagram

6. Project Results

  • After the retrofit, the power factor remained at the target value of 0.99 (inductive) in both standby and charging operation.
  • The standby capacitive condition was avoided.
  • Compared with before the retrofit, the monthly power-factor adjustment reward increased by RMB 3,200 per transformer.
  • For the two transformers, the annual saving was RMB 76,000, with the investment recovered within two years.
  • SVG compensation reduced part of the line loss, increased the terminal line voltage, and improved the stability and safety of the line system.