Apparel & Footwear Wholesale Market – Excessive Neutral Current & Harmonic Distortion
APF harmonic mitigation case
Industry Apparel & footwear wholesale Market |
Main load LED lighting / LED display screens |
Transformer 2500 kVA |
APF installation 2 × 200 A |
Measurement load rate 90% |
Existing compensation 600 kvar |
1. Project Background
The building has eight floors. Floors 1–2 contain a large number of shops, and the main floor loads are LED lighting. Property management reported that, when the three phase currents were similar, the neutral-line current at the Floor 1 and Floor 2 main switches was higher than the phase current. Because the neutral conductor was smaller than the phase conductors, long-term operation presented an overheating and fire risk.
The transformer circuit is rated at 2500 kVA. The main equipment includes LED lighting and LED display screens. The circuit is equipped with two compensation cabinets with a total capacity of 600 kvar. During measurement, the load rate was 90%. One 200 A APF was installed at the Floor 1 main incoming switch and one at the Floor 2 main incoming switch.

2. Measurement Purpose
The measurement was carried out after the two 200 A APFs on the Floor 1 and Floor 2 main incoming switches were put into operation, to verify whether the filtering effect met the expected result.
3. Floor 1 Measured Results
| APF status |
3rd (A) |
5th (A) |
7th (A) |
THD (A) |
N-line (A) |
ITHD |
VTHD |
| Off |
133.02 |
39.88 |
20.29 |
141.77 |
367.6 |
52.64% |
5.30% |
| On |
9.02 |
5.38 |
3.54 |
16.88 |
25.19 |
5.08% |
4.05% |

4. Floor 2 Measured Results
| APF status |
3rd (A) |
5th (A) |
7th (A) |
THD (A) |
N-line (A) |
ITHD |
VTHD |
| Off |
135.42 |
39.93 |
27.88 |
145.41 |
360.6 |
58.24% |
5.30% |
| On |
6.14 |
8.22 |
6.93 |
17.4 |
19.54 |
6.88% |
4.05% |

5. Main Incoming Switch Measured Results
| APF status |
3rd (A) |
5th (A) |
7th (A) |
THD (A) |
N-line (A) |
ITHD |
VTHD |
| Off |
842.4 |
199.83 |
132.55 |
850.7 |
2245.7 |
40.85% |
5% |
| On |
671 |
181.9 |
77.38 |
704.1 |
1733 |
33.12% |
4.20% |
6. Result Summary
- For the Floor 1 main switch, the report states that the zero-sequence harmonic mitigation effect after the APF was put into operation was very obvious, and the filter display data were basically consistent with the measured data.
- For the Floor 2 main switch, the report gives the same conclusion: the zero-sequence harmonic mitigation effect was very obvious, and the filter display data were basically consistent with the measured data.
- At the main incoming switch, after the APFs on Floors 1 and 2 were put into operation, the N-line apparent current decreased from 2245.7 A to 1733 A, a reduction of 512.7 A in zero-sequence harmonic current.
- The report states that, if the total-circuit harmonic current is to be reduced to the ideal effect, sufficient APF capacity needs to be installed at each floor and in the main distribution room.
7. Filter Display Records
The report states that the filter display data were basically consistent with the measured data.

Filter-screen records before and after treatment.
8. Conclusion
The report concludes that the filtering retrofit results from installing active power filters at the Floor 1 and Floor 2 main switches were relatively satisfactory and met the acceptance conditions.