Power Factor Correction Solution for Copper Alloy Manufacturing Plant
Subtitle: SVG Reactive Power Compensation & Capacitor Bank Retrofit
Industry
Copper Processing / Non-Ferrous Metal Manufacturing
Project Overview
The customer operates a copper alloy manufacturing park with an annual production capacity of 50,000 tons. The facility is equipped with four 800 kVA transformers, each connected to a photovoltaic system.
Challenge
The main production workshop uses a large number of variable-frequency drives, resulting in significant harmonic distortion and unstable reactive power demand. The existing capacitor banks frequently tripped, and the power factor remained at around 0.7, leading to monthly power-factor penalties of approximately RMB 8,000.
Solution
Based on onsite measurements, the plant had an estimated reactive power deficit of approximately 700 kvar. The retrofit included:
- 4 × 100 kvar SVG units
- 400 kvar additional reactive power compensation
- 7% series reactors added to the existing capacitor banks
- Dynamic reactive power compensation to accommodate rapidly changing loads and PV generation
Results
After the retrofit:
- Power factor increased from approximately 0.70 to around 1.00
- Utility-meter power factor remained above 0.95
- Monthly power-factor penalties were eliminated
- In the first month after commissioning, the customer received a power-factor incentive of more than RMB 500 instead of an approximately RMB 8,000 penalty
Result Highlight
PF 0.70 → 0.95+
RMB 8,000+/month penalty → Eliminated