APF Harmonic Mitigation for Medium-Frequency Induction Furnace Loads
PROJECT CASE | POWER QUALITY
Optimized active harmonic filtering for a tungsten & molybdenum manufacturing line
INDUSTRY Tungsten & Molybdenum Processing |
APPLICATION Medium-Frequency Induction Furnace |
SOLUTION Active Power Filter (APF) |
Project Background
A tungsten and molybdenum production line uses medium-frequency induction furnaces for metal processing. During operation, the furnaces generated highly distorted current with a broad harmonic spectrum, degrading power quality and interfering with surrounding electrical equipment.

Power Quality Challenge
- The furnace current waveform was strongly distorted and rich in harmonics.
- Thyristor commutation produced pronounced voltage notching and fast current changes.
- An initial APF installation improved the waveform, but oscillation occurred during startup and loaded operation.

Field Diagnosis
On-site waveform analysis confirmed severe current distortion. The diagnostic snapshot below shows phase current THD of approximately 30.5%–31.8%, while the 5th harmonic alone was approximately 23.4%–24.0% at the measured operating point.
30.5–31.8% Current THD during field diagnosis |
23.4–24.0% 5th harmonic share at the captured point |
≈40–41 A 5th harmonic current shown in the snapshot |
 Current THD during diagnosis |
 5th harmonic spectrum during diagnosis |
The site also experienced deep voltage notches during commutation. The previous RC absorption circuit had been removed after repeated failures.
 Measurement setup |
 Voltage waveform |
 Current waveform |
Optimized APF Solution
- Increase the APF output line-frequency inductance to reduce sensitivity to high-frequency voltage notches.
- • Optimize output-current fault detection .
- Refine the shutdown sequence so output current decays before relay disconnection.
Implementation & Results
After hardware and control-logic optimization, the APF operated stably with the induction-furnace load. The project report records stable startup without oscillation, stable operation under load changes, and THDi reduced to within the grid harmonic requirement referenced by the project.

APF installed at the induction-furnace application
 APF operating interface during field verification |
 Load-side operating data during verification |
Project Outcomes
Stable Startup Startup became smooth with no reported oscillation. |
Stable Under Load The APF remained stable and responded rapidly to load changes. |
Lower Harmonic Distortion THDi was reduced to within the grid requirement referenced in the project report. |
Improved Reliability Optimized monitoring and protection reduced nuisance faults and improved operational safety. |