Water Supply – High Harmonic Distortion from VFD Loads
PROJECT CASE
Industry
Water Supply |
Transformer
2 × 1000 kVA |
Main Loads
VFDs and Motors |
VFD Loads
3 groups |
Rated Power
250 kW per group |
Measurement Date
2025-04-02 |
1. Project Background
The project involved a state-owned water supply facility. The distribution system has two 1000 kVA transformers, with one in service and one on standby, connected through a bus-tie cabinet. The loads include VFDs and motors. There are three VFD groups, each rated at 250 kW.
Power quality measurements were taken at the defined measurement point to record bus voltage, current, power and harmonic conditions.

2. Initial Measurement
The report recorded a total voltage harmonic distortion of 8% and a total current harmonic distortion of 60%.

Initial voltage and current harmonic distortion measurements
| 5th Harmonic |
7th Harmonic |
11th Harmonic |
13th Harmonic |
| 480 A |
230 A |
200 A |
180 A |

3. APF Configuration
The equipment list in the report specifies the following APF configuration:
- 4 × 200 A active power filters
- 1 × 150 A active power filter
4. Post-Treatment Measurement
The post-treatment measurements recorded in the report are shown below.
| Measured Item |
Initial Measurement |
Post-Treatment Measurement |
| Voltage THD |
8% |
3% |
| Current THD |
60% |
14% |
| 5th harmonic current |
480 A |
40 A |
| 11th harmonic current |
200 A |
30 A |
| 13th harmonic current |
180 A |
<20 A |


Post-treatment 5th, 11th and 13th harmonic-current measurements