Water Supply – High Harmonic Distortion from VFD Loads

PROJECT CASE

 

Industry
Water Supply
Transformer
2 × 1000 kVA
Main Loads
VFDs and Motors
VFD Loads
3 groups
Rated Power
250 kW per group
Measurement Date
2025-04-02

1. Project Background

The project involved a state-owned water supply facility. The distribution system has two 1000 kVA transformers, with one in service and one on standby, connected through a bus-tie cabinet. The loads include VFDs and motors. There are three VFD groups, each rated at 250 kW.

Power quality measurements were taken at the defined measurement point to record bus voltage, current, power and harmonic conditions.

2. Initial Measurement

The report recorded a total voltage harmonic distortion of 8% and a total current harmonic distortion of 60%.

Initial voltage and current harmonic distortion measurements

5th Harmonic 7th Harmonic 11th Harmonic 13th Harmonic
480 A 230 A 200 A 180 A

3. APF Configuration

The equipment list in the report specifies the following APF configuration:

  • 4 × 200 A active power filters
  • 1 × 150 A active power filter

4. Post-Treatment Measurement

The post-treatment measurements recorded in the report are shown below.

Measured Item Initial Measurement Post-Treatment Measurement
Voltage THD 8% 3%
Current THD 60% 14%
5th harmonic current 480 A 40 A
11th harmonic current 200 A 30 A
13th harmonic current 180 A <20 A

Post-treatment 5th, 11th and 13th harmonic-current measurements