APF Harmonic Mitigation for a Data Center Power Distribution System

PROJECT CASE | DATA CENTER

500 A APF retrofit on the TR1 circuit to suppress harmonics generated by VFD-driven cooling and auxiliary equipment.

INDUSTRY
Data Center
APPLICATION
TR1 Circuit
SOLUTION
500 A APF
TEST CURRENT
200-850 A
26.94% → 3.12%
THDi
204.96 A → 15.28 A
5th Harmonic
60.50 A → 10.14 A
7th Harmonic
3.65% → 1.10%
VTHD

Project Context

The TR1 circuit is supplied by a 2,000 kVA transformer and serves loads including variable-frequency drives, air compressors, chilled-water/cooling equipment. During acceptance testing, circuit current varied from approximately 200 A to 850 A, with the highest harmonic levels observed under heavier loading.

Original single-line diagram showing the TR1 measurement point and the 500 A APF retrofit location.

Challenge

  • High nonlinear loading from VFD-based equipment produced substantial current harmonics on the TR1 circuit.
  • With the APF disconnected, the report recorded THDi at 26.94%, 5th harmonic current at 204.96 A, 7th harmonic current at 60.50 A, and VTHD at 3.65%.
  • The retrofit needed to reduce harmonic injection under real operating conditions and satisfy the acceptance criteria referenced to GB/T 14549.

Solution

A 500 A active power filter system was integrated into the TR1 filter cabinet. Acceptance testing switched the filter in and out while a power-quality analyzer recorded current, voltage and harmonic behavior.

Installed APF filter cabinets and modular arrangement at the TR1 circuit.

Dynamic Test Evidence

Measured Performance

The acceptance table below is the primary numerical basis for the before/after values used in this case. It directly identifies the TR1 measurements with the APF disconnected and connected.

Harmonic Reduction Evidence

The 5th and 7th harmonics were the dominant components during the high-distortion condition.

Spectrum Comparison

Project Outcome

  • Total harmonic current: 219.36 A → 19.18 A.
  • THDi: 26.94% → 3.12%; VTHD: 3.65% → 1.10%.
  • 5th harmonic current: 204.96 A → 15.28 A; 7th harmonic current: 60.50 A → 10.14 A.
  • The acceptance report concluded that the measured harmonics met the GB/T 14549 requirements referenced for the project and that the system satisfied the acceptance conditions.