Get A Quote

Home > Products > PFC Components > Reactive Power Controller > Smart Capacitor Bank Controller

return

ZKY42 / ZKY32

Smart Capacitor Bank Controller

Smart Capacitor Bank Controller

Reactive power compensation monitoring and control for low-voltage distribution systems. Functions and ratings vary by model.

Product Advantages

  • ZKY42 / ZKY32 Models On This Page
  • ≤32 units Zky32 Controlled Units
  • 65°C / 55°C Max Ambient Temperature
  • 2500 m / 2000 m Max Installation Altitude

Technological breakthrough

Model Specification Comparison

Operating limits and enclosure dimensions

Model Specification Comparison

ZKY42 ZKY32
1. Maximum Ambient Temperature Official data
ZKY42
65°C
ZKY32
55°C
2. Maximum Installation Altitude Official data
ZKY42
2500 m
ZKY32
2000 m
3. Overall Enclosure Depth Official data
ZKY42
80 mm
ZKY32
100 mm

Why It Matters

  • 1
    ZKY42 Harmonic Display

    Voltage / current THD and individual harmonics from the 2nd to the 15th order.

  • 2
    ZKY32 Intelligent Capacitor Control

    Controls up to 32 common or individual-phase intelligent capacitor units.

  • 3
    Check the Panel Cutout

    ZKY42: 113 x 113 mm. ZKY32:112 x 112 mm. Select the supply and wiring for the chosen model.

Core Advantages

Three Phase System Monitoring

View phase voltage, current, power factor, active power and reactive power to assess compensation requirements.

Integrated Measurement and Control

ZKY42 uses digital signal processing and AC sampling. ZKY32 uses a dedicated metering IC for measurement and capacitor control.

Automatic and Manual Operation

Use automatic compensation during service and manual switching when checking individual capacitor steps.

Compensation Configuration Choices

ZKY42 supports Y, delta and combined Y plus delta compensation. ZKY32 supports common and individual-phase intelligent capacitor units.

Protection for Abnormal Conditions

Both models provide overvoltage and undervoltage protection. ZKY42 adds low-current and voltage-harmonic protection, while ZKY32 includes overtemperature protection.

Harmonic Analysis on ZKY42

ZKY42 displays voltage and current THD, together with individual harmonic content from the 2nd through the 15th order.

Stored Settings on ZKY42

ZKY42 automatically saves parameter changes and retains the settings after power loss.

Automatic Networking on ZKY32

ZKY32 automatically networks with connected intelligent capacitor units during its default two-minute power-up delay.

Product Applications

LV distribution

Reactive-power monitoring and control

System monitoring

Voltage, current and power factor

ZKY42 compensation

Y, delta or combined Y plus delta

ZKY32 capacitor units

Up to 32 intelligent capacitor units

Automatic compensation

Automatic control in normal operation

Manual switching

Manual switching of capacitor steps

Abnormal protection

Overvoltage and undervoltage protection

ZKY42 harmonics

THD and 2nd–15th harmonic display

Automatic networking

Auto-network on the power-up delay

Panel-mount install

113 × 113 mm or 112 × 112 mm cutouts

ZKY42 Electrical Ratings

Power Supply Sampling Voltage Frequency Sampling Current
AC 380 V ±20% AC 220 V ±20% 50 Hz / 60 Hz ±2% 0-5 A

ZKY42 Measurement Accuracy

Voltage Current Active Power Reactive Power Power Factor
±1% ±1% ±2.5% ±2.5% ±1.5%

Common Specifications

Voltage and current THD display; individual voltage and current harmonics: 2nd-15th.

Compensation configurations: Y, delta and Y + delta. Automatic, manual and simulation operation.

ZKY32 Electrical and Control Ratings

Operating Voltage Frequency Voltage Distortion Controlled Units
220 V ±20% 50 Hz / 60 Hz ≤20% ≤32 common / individual-phase intelligent capacitor units

ZKY32 Measurement Accuracy

Voltage Current Power Factor Reactive Power
±1% ±1% ±0.01 ±2%

Operating Conditions and Installation

Model Ambient Temperature Relative Humidity Altitude Overall Dimensions Panel Cutout
ZKY42 -25°C to +65°C ≤90% at 20°C ≤2500 m 120 × 120 × 80 mm 113 × 113 mm
ZKY32 -25°C to +55°C 20-90% at 40°C ≤2000 m 120 × 120 × 100 mm 112 × 112 mm

Common Specifications

ZKY42 mounting depth: 70 mm.

Use the sampling and control wiring specified for the selected model.

Please Share the Details You Know:

  • Product or model
  • Application or problem to solve
  • Required specifications, such as voltage, frequency or capacity
  • Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements

FAQ

How do I choose between ZKY42 and ZKY32?

ZKY42 is suited to projects that need three-phase electrical measurements, harmonic display and compensation control. ZKY32 is intended for controlling compatible networked compensation units. Share the connected capacitor or switch model so we can check the configuration.

Can ZKY42 display harmonic data?

Yes. It displays voltage and current THD by phase, plus individual voltage and current harmonics from the 2nd to the 15th order.

Which compensation connections does ZKY42 support?

Its manual lists Y-connected, Δ-connected and combined Y + Δ compensation. The selected setting must match the actual wiring.

How many units can ZKY32 control?

The ZKY32 manual specifies up to 32 compatible common or individual-phase intelligent capacitor units.

How does ZKY32 decide when to switch capacitors?

It uses reactive power as the switching criterion and provides automatic and manual operating modes.

What protection functions are listed?

ZKY42 lists over-voltage, under-voltage, low-current and voltage-THD limit protection. ZKY32 lists over-voltage, under-voltage and over-temperature protection.