JKWF-12

Three Phase Power Factor Controller

Three Phase Power Factor Controller

A three-phase reactive-power controller with configurable capacitor steps and static or dynamic outputs.

Product Advantages

  • Three-phase Ac Sampling
  • 1-12 Control Circuits
  • Static / Dynamic Output Options
  • 47-53 Hz Frequency (As Printed)

Core Advantages

Three-phase AC sampling

Samples voltage and current on all three phases.

Live operating data

Displays power factor, voltage, current, reactive power and capacitor switching status, with a data refresh interval of no more than one second.

Two Compensation Strategies

Select power-factor cyclic switching or reactive-power-based compensation. Reactive power control can skip an oversized step to avoid overcompensation.

Automatic and Manual Control

Automatic operation follows the configured compensation settings. Manual operation allows individual switching checks during commissioning.

Individual Step Configuration

Set capacitor capacity and phase assignment by circuit to suit common or individual-phase compensation arrangements.

Up to Twelve Control Circuits

Configure between one and twelve capacitor control circuits to match the number of installed steps.

Static or Dynamic Output Options

Choose relay contacts for contactor switching or 12 V DC outputs for compatible composite or thyristor switching devices.

Alarm and Protection Functions

Overvoltage, undervoltage and zero-current alarms inhibit switching when the corresponding abnormal condition is detected.

Product Applications

LV cabinets

Three-phase V and I sampling

Balanced loads

Common-compensation step control

Unbalanced loads

Individual-phase step assignment

Contactor switching

Relay contacts 5 A / 250 V

Dynamic switching

DC 12 V, 30 mA outputs

Auto compensation

Follows configured control settings

Manual switching

Step checks during commissioning

Step counts

One to twelve control circuits

Alarm protection

OV, UV and zero-current inhibit

Panel-mount install

Cutout 113 × 113 mm, depth 95 mm

Electrical Ratings

Power Supply Measured Voltage Frequency CT Secondary Input
380 V ±20% 100-500 V 47-53 Hz 0-5 A

Measurement and Display

Voltage / Current Accuracy Active / Reactive Power Accuracy Power Factor Accuracy Data Refresh
±0.5% ±1.0% ±1.0% ≤1 s

Common Specifications

Primary current measurement: 0-6000 A. Secondary-current sensitivity: 50 mA.

Measured power factor: 0.200 lagging to 0.200 leading. Active power: 0-6553 kW; reactive power: 0-6553 kvar.

Control Output Options

Configuration Output Control Circuits Compensation Control
Static Relay dry contacts: 5 A / 250 V, resistive load 1-12 Power factor / reactive power control
Dynamic DC 12 V, 30 mA per circuit 1-12 Power factor / reactive power control

Common Specifications

Static or dynamic output configuration shall be specified when ordering.

Common or individual-phase capacitor-step assignment. Overvoltage, undervoltage and zero-current alarm protection.

Operating Conditions

Ambient Temperature Storage Temperature Altitude
-20°C to +60°C -40°C to +70°C ≤2500 m

Common Specifications

Installation environment: no corrosive gas, conductive dust, flammable or explosive medium, severe vibration, or rain / snow ingress.

Installation

Panel Cutout Embedded Depth
113 × 113 mm 95 mm

Please Share the Details You Know:

  • Product or model
  • Application or problem to solve
  • Required specifications, such as voltage, frequency or capacity
  • Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements

FAQ

How many capacitor steps does JKWF12 support?

It supports up to 12 control circuits.

Can I combine three-phase and individual-phase compensation?

Yes. Each circuit can be assigned to three-phase compensation or to phase A, B or C, with its capacity set separately.

Can JKWF12 be used with contactors or composite switches?

The manual describes relay contact output for static control and 12 V output for dynamic control. Specify the switching device and control method when ordering.

Does it offer both power-factor and reactive-power control?

Yes. Both modes are available through the controller settings.

How does it reduce the risk of overcompensation?

In reactive-power control mode, it checks whether a proposed step would cause overcompensation. If possible, it selects a smaller available step instead.

What should be checked if automatic switching stops?

Check for over-voltage, under-voltage or low-current alarms, and verify that voltage and current sampling follow the correct phase sequence.