Live Grid Monitoring
The Chinese and English LCD displays voltage, current, power factor, active and reactive power, harmonic distortion, frequency and capacitor switching status.
JKWF24
LCD Power Factor Controller
A reactive-power compensation controller for LV capacitor banks, with configurable outputs and mixed compensation.
Product Advantages
The Chinese and English LCD displays voltage, current, power factor, active and reactive power, harmonic distortion, frequency and capacitor switching status.
Reactive power sampling guides capacitor-step selection to reduce switching oscillation and compensation dead zones.
Set the capacitor capacity of each output circuit to match the installed bank.
Supports common three-phase compensation and mixed delta plus star compensation for different capacitor-bank arrangements.
Automatic switching follows configured settings, while manual mode allows individual capacitor steps to be checked.
Provides overvoltage, undervoltage, voltage and current harmonic, low-current and low power factor protection, with alarm indication.
Non-volatile memory retains configuration settings after a power interruption.
RS485 supports host data upload and remote switching. Statistics and MODBUS functions are available according to the selected configuration.
Reactive-power bank control
Common three-phase arrangements
Delta plus star bank arrangements
Automatic switching in service
Manual checks of capacitor steps
12, 16, 18 or 24 output circuits
DC 12 V or relay, by model
OV, UV, harmonic, low-I and low-PF
RS485 upload and remote switching
144 × 144 mm, cutout 138 × 138 mm
| System Voltage | Frequency | Sampling Current | Power Consumption |
|---|---|---|---|
| AC 400 V ±20% | 50 Hz / 60 Hz ±5% | 0-5 A | 6 W |
| Voltage | Current | Frequency | Power Factor | Active Power | Reactive Power |
|---|---|---|---|---|---|
| ±0.5% | ±0.5% | ±0.1% | ±1.0% | ±1.0% | ±1.0% |
| Output Circuit Options | Maximum DC Drive per Output | Current Sampling Sensitivity |
|---|---|---|
| 12 / 16 / 18 / 24 | DC 12 V, 50 mA | 10 mA |
Common Specifications
Output type: DC 12 V or relay, according to model. Common three-phase or mixed delta + star compensation.
RS485 interface; MODBUS protocol and operating statistics depend on configuration.
| Switch-in Delay | Switch-out Delay | Capacitor Discharge Time |
|---|---|---|
| 0-99.9 s | 0-99.9 s | 0-999 s |
Common Specifications
Automatic and manual control. Capacitor capacity is configurable for each output circuit.
Protection: overvoltage, undervoltage, voltage / current harmonics, low current and low power factor. Settings are retained after power loss.
| Ambient Temperature | Relative Humidity | Altitude | Atmospheric Pressure |
|---|---|---|---|
| -20°C to +65°C | 20-90% at 40°C | ≤2500 m | 79.5-106 kPa |
Common Specifications
No explosive hazard, corrosive or insulation-damaging gases, conductive dust, severe vibration, or rain / snow ingress.
Standards: JB/T 9663-2013; DL/T 597-1996.
| Front Dimensions | Body Depth | Panel Cutout |
|---|---|---|
| 144 × 144 mm | 80.5 mm | 138 × 138 mm |
You can also attach drawings, product photos or test reports, if available.
The series lists 12, 16, 18 and 24-circuit configurations. Select the version that matches the panel’s capacitor steps.
Yes. The manual lists Δ + Y mixed compensation and common three-phase compensation.
Yes. Capacitor-bank capacity can be configured individually for each circuit.
The display shows power factor, voltage, current, active and reactive power, voltage/current harmonic distortion, frequency, switching status and alarms.
The manual lists over-voltage, under-voltage, voltage/current harmonic, small-current and low power-factor protection. Check the selected settings for the project.
Communication and statistics depend on the configuration. Confirm RS485 and MODBUS requirements when ordering.