JKW5C / JKW5D

12-Step Power Factor Controller

12-Step Power Factor Controller

Automatic compensation controllers for low-voltage capacitor banks, with relay or DC control outputs according to model.

Product Advantages

  • AC 220 V or 380 V Operating Voltage
  • 4-16 Control Circuits
  • Relay or DC Output Options
  • IP40 Enclosure Rating

Core Advantages

Reactive-power selection

Calculates the capacitor capacity required from reactive power to improve compensation accuracy and reduce switching oscillation.

Two Selectable Control Modes

Choose power factor control or reactive power control to suit the load and capacitor-bank configuration.

Wide Power Factor Display

Displays both lagging and leading power factor so operators can identify undercompensation and overcompensation.

Software Phase Adjustment

The initial phase preset allows current-signal polarity adjustment through software during commissioning.

Digital Parameter Settings

Adjust thresholds, switching delays, CT ratio and capacitor-step capacities through the digital interface.

Automatic and Manual Operation

Run automatic compensation in service and use manual switching to check capacitor steps.

Voltage Protection

Overvoltage and undervoltage protection help prevent capacitor operation outside the configured voltage limits.

Power Failure Memory

Retains stored settings after power loss, reducing the need to re-enter commissioning data.

Product Applications

LV capacitor banks

Automatic compensation control

Relay-output switching

JKW5C relay contacts, AC 220 V, 7 A

DC-output switching

JKW5D negative DC, +12 V common

Power-factor mode

Control from configured PF settings

Reactive-power mode

Step selection from measured kVAr

Automatic compensation

Automatic control in normal operation

Manual switching

Manual checks of capacitor steps

Phase adjustment

Current polarity via initial-phase preset

Voltage protection

Inhibit steps outside set voltage limits

IP40 installations

Use within the printed IP40 rating

Electrical Ratings

Operating Voltage Frequency Current Input Sensitivity Enclosure Rating
AC 220 V or 380 V 50 Hz / 60 Hz AC 0-5 A 60 mA IP40

Control Output Options

Model Output Type Interface / Rating Control Circuits
JKW5C Relay contacts AC 220 V, 7 A, 50 Hz 4-16, depending on model
JKW5D Negative DC control signals +12 V common terminal 4-16, depending on model

Common Specifications

Control modes: power factor or reactive power. Automatic and manual operation.

In reactive power control mode, enter the actual CT ratio and capacitor capacity of each step.

Measurement and Settings

Power Factor Display Reactive Power Measurement Switching Delay Setting Current Input Impedance
0.001 lagging to 0.001 leading 0-9999 kvar 1-250 s <0.01 Ω

Common Specifications

Overvoltage setting range: 230-260 V or 380-500 V, according to voltage configuration.

Reactive power mode: CT preset 50-5000; capacitor capacity setting 0-150.0 kvar per circuit.

Operating Conditions

Ambient Temperature Relative Humidity Altitude
-25°C to +50°C ≤50% at 40°C · ≤90% at 20°C ≤2500 m

Common Specifications

No corrosive gas, conductive dust, flammable / explosive medium, or severe vibration.

Standard: JB/T 9663-2013.

Please Share the Details You Know:

  • Product or model
  • Application or problem to solve
  • Required specifications, such as voltage, frequency or capacity
  • Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements

FAQ

What is the difference between JKW5C and JKW5D?

JKW5C provides relay contact outputs. JKW5D provides negative DC control-signal outputs with a +12 V common terminal. Choose the version that matches the switching device.

How many capacitor steps can the controller manage?

The series offers 4 to 16 control circuits, depending on the model. Confirm the required number of steps when ordering.

Can it control switching by either power factor or reactive power?

Yes. Both control modes are available, but the controller operates in one mode at a time.

What must be set in reactive-power control mode?

Enter the actual CT ratio and the capacity of each connected capacitor step. Incorrect values can affect switching decisions.

Can capacitor steps be operated manually?

Yes. Manual mode can be used to check step switching during commissioning.

Will settings be lost after a power failure?

No. The manual states that stored settings are retained after power loss.