Get A Quote

JKWF24

LCD Power Factor Controller

LCD Power Factor Controller

A reactive-power compensation controller for LV capacitor banks, with configurable outputs and mixed compensation.

Product Advantages

  • 12 / 16 / 18 / 24 Output Circuit Options
  • 144 × 144 mm Front Dimensions
  • AC 400 V ±20% System Voltage
  • Chinese / English LCD Display

Core Advantages

Live Grid Monitoring

The Chinese and English LCD displays voltage, current, power factor, active and reactive power, harmonic distortion, frequency and capacitor switching status.

Reactive Power Based Control

Reactive power sampling guides capacitor-step selection to reduce switching oscillation and compensation dead zones.

Individual Capacitor Step Settings

Set the capacitor capacity of each output circuit to match the installed bank.

Common and Mixed Compensation

Supports common three-phase compensation and mixed delta plus star compensation for different capacitor-bank arrangements.

Automatic and Manual Operation

Automatic switching follows configured settings, while manual mode allows individual capacitor steps to be checked.

Protection for Abnormal Conditions

Provides overvoltage, undervoltage, voltage and current harmonic, low-current and low power factor protection, with alarm indication.

Settings Retained after Power Loss

Non-volatile memory retains configuration settings after a power interruption.

Communication and Operating Statistics

RS485 supports host data upload and remote switching. Statistics and MODBUS functions are available according to the selected configuration.

Product Applications

LV capacitor banks

Reactive-power bank control

Common three-phase

Common three-phase arrangements

Mixed compensation

Delta plus star bank arrangements

Automatic control

Automatic switching in service

Manual switching

Manual checks of capacitor steps

Output counts

12, 16, 18 or 24 output circuits

DC or relay outputs

DC 12 V or relay, by model

Alarm protection

OV, UV, harmonic, low-I and low-PF

Host communication

RS485 upload and remote switching

Panel-mount install

144 × 144 mm, cutout 138 × 138 mm

Technical Parameters

Electrical Ratings

System Voltage Frequency Sampling Current Power Consumption
AC 400 V ±20% 50 Hz / 60 Hz ±5% 0-5 A 6 W

Measurement Accuracy

Voltage Current Frequency Power Factor Active Power Reactive Power
±0.5% ±0.5% ±0.1% ±1.0% ±1.0% ±1.0%

Control and Communication

Output Circuit Options Maximum DC Drive per Output Current Sampling Sensitivity
12 / 16 / 18 / 24 DC 12 V, 50 mA 10 mA

Common Specifications

Output type: DC 12 V or relay, according to model. Common three-phase or mixed delta + star compensation.

RS485 interface; MODBUS protocol and operating statistics depend on configuration.

Switching Settings

Switch-in Delay Switch-out Delay Capacitor Discharge Time
0-99.9 s 0-99.9 s 0-999 s

Common Specifications

Automatic and manual control. Capacitor capacity is configurable for each output circuit.

Protection: overvoltage, undervoltage, voltage / current harmonics, low current and low power factor. Settings are retained after power loss.

Operating Conditions

Ambient Temperature Relative Humidity Altitude Atmospheric Pressure
-20°C to +65°C 20-90% at 40°C ≤2500 m 79.5-106 kPa

Common Specifications

No explosive hazard, corrosive or insulation-damaging gases, conductive dust, severe vibration, or rain / snow ingress.

Standards: JB/T 9663-2013; DL/T 597-1996.

Installation

Front Dimensions Body Depth Panel Cutout
144 × 144 mm 80.5 mm 138 × 138 mm

Please Share the Details You Know:

  • Product or model
  • Application or problem to solve
  • Required specifications, such as voltage, frequency or capacity
  • Quantity and delivery requirements

You can also attach drawings, product photos or test reports, if available.

Share Your Requirements

FAQ

How many output circuits are available?

The series lists 12, 16, 18 and 24-circuit configurations. Select the version that matches the panel’s capacitor steps.

Does it support mixed compensation?

Yes. The manual lists Δ + Y mixed compensation and common three-phase compensation.

Can the capacity of each capacitor circuit be set?

Yes. Capacitor-bank capacity can be configured individually for each circuit.

What can operators view on the LCD?

The display shows power factor, voltage, current, active and reactive power, voltage/current harmonic distortion, frequency, switching status and alarms.

What protection functions does it provide?

The manual lists over-voltage, under-voltage, voltage/current harmonic, small-current and low power-factor protection. Check the selected settings for the project.

Can it communicate with a monitoring system?

Communication and statistics depend on the configuration. Confirm RS485 and MODBUS requirements when ordering.