Reactive-power selection
Calculates the capacitor capacity required from reactive power to improve compensation accuracy and reduce switching oscillation.
JKW5C / JKW5D
12-Step Power Factor Controller
Automatic compensation controllers for low-voltage capacitor banks, with relay or DC control outputs according to model.
Product Advantages
Calculates the capacitor capacity required from reactive power to improve compensation accuracy and reduce switching oscillation.
Choose power factor control or reactive power control to suit the load and capacitor-bank configuration.
Displays both lagging and leading power factor so operators can identify undercompensation and overcompensation.
The initial phase preset allows current-signal polarity adjustment through software during commissioning.
Adjust thresholds, switching delays, CT ratio and capacitor-step capacities through the digital interface.
Run automatic compensation in service and use manual switching to check capacitor steps.
Overvoltage and undervoltage protection help prevent capacitor operation outside the configured voltage limits.
Retains stored settings after power loss, reducing the need to re-enter commissioning data.
Automatic compensation control
JKW5C relay contacts, AC 220 V, 7 A
JKW5D negative DC, +12 V common
Control from configured PF settings
Step selection from measured kVAr
Automatic control in normal operation
Manual checks of capacitor steps
Current polarity via initial-phase preset
Inhibit steps outside set voltage limits
Use within the printed IP40 rating
| Operating Voltage | Frequency | Current Input | Sensitivity | Enclosure Rating |
|---|---|---|---|---|
| AC 220 V or 380 V | 50 Hz / 60 Hz | AC 0-5 A | 60 mA | IP40 |
| Model | Output Type | Interface / Rating | Control Circuits |
|---|---|---|---|
| JKW5C | Relay contacts | AC 220 V, 7 A, 50 Hz | 4-16, depending on model |
| JKW5D | Negative DC control signals | +12 V common terminal | 4-16, depending on model |
Common Specifications
Control modes: power factor or reactive power. Automatic and manual operation.
In reactive power control mode, enter the actual CT ratio and capacitor capacity of each step.
| Power Factor Display | Reactive Power Measurement | Switching Delay Setting | Current Input Impedance |
|---|---|---|---|
| 0.001 lagging to 0.001 leading | 0-9999 kvar | 1-250 s | <0.01 Ω |
Common Specifications
Overvoltage setting range: 230-260 V or 380-500 V, according to voltage configuration.
Reactive power mode: CT preset 50-5000; capacitor capacity setting 0-150.0 kvar per circuit.
| Ambient Temperature | Relative Humidity | Altitude |
|---|---|---|
| -25°C to +50°C | ≤50% at 40°C · ≤90% at 20°C | ≤2500 m |
Common Specifications
No corrosive gas, conductive dust, flammable / explosive medium, or severe vibration.
Standard: JB/T 9663-2013.
You can also attach drawings, product photos or test reports, if available.
JKW5C provides relay contact outputs. JKW5D provides negative DC control-signal outputs with a +12 V common terminal. Choose the version that matches the switching device.
The series offers 4 to 16 control circuits, depending on the model. Confirm the required number of steps when ordering.
Yes. Both control modes are available, but the controller operates in one mode at a time.
Enter the actual CT ratio and the capacity of each connected capacitor step. Incorrect values can affect switching decisions.
Yes. Manual mode can be used to check step switching during commissioning.
No. The manual states that stored settings are retained after power loss.