Three Phase System Monitoring
View phase voltage, current, power factor, active power and reactive power to assess compensation requirements.
ZKY42 / ZKY32
Smart Capacitor Bank Controller
Reactive power compensation monitoring and control for low-voltage distribution systems. Functions and ratings vary by model.
Product Advantages
Operating limits and enclosure dimensions
Voltage / current THD and individual harmonics from the 2nd to the 15th order.
Controls up to 32 common or individual-phase intelligent capacitor units.
ZKY42: 113 x 113 mm. ZKY32:112 x 112 mm. Select the supply and wiring for the chosen model.
View phase voltage, current, power factor, active power and reactive power to assess compensation requirements.
ZKY42 uses digital signal processing and AC sampling. ZKY32 uses a dedicated metering IC for measurement and capacitor control.
Use automatic compensation during service and manual switching when checking individual capacitor steps.
ZKY42 supports Y, delta and combined Y plus delta compensation. ZKY32 supports common and individual-phase intelligent capacitor units.
Both models provide overvoltage and undervoltage protection. ZKY42 adds low-current and voltage-harmonic protection, while ZKY32 includes overtemperature protection.
ZKY42 displays voltage and current THD, together with individual harmonic content from the 2nd through the 15th order.
ZKY42 automatically saves parameter changes and retains the settings after power loss.
ZKY32 automatically networks with connected intelligent capacitor units during its default two-minute power-up delay.
Reactive-power monitoring and control
Voltage, current and power factor
Y, delta or combined Y plus delta
Up to 32 intelligent capacitor units
Automatic control in normal operation
Manual switching of capacitor steps
Overvoltage and undervoltage protection
THD and 2nd–15th harmonic display
Auto-network on the power-up delay
113 × 113 mm or 112 × 112 mm cutouts
| Power Supply | Sampling Voltage | Frequency | Sampling Current |
|---|---|---|---|
| AC 380 V ±20% | AC 220 V ±20% | 50 Hz / 60 Hz ±2% | 0-5 A |
| Voltage | Current | Active Power | Reactive Power | Power Factor |
|---|---|---|---|---|
| ±1% | ±1% | ±2.5% | ±2.5% | ±1.5% |
Common Specifications
Voltage and current THD display; individual voltage and current harmonics: 2nd-15th.
Compensation configurations: Y, delta and Y + delta. Automatic, manual and simulation operation.
| Operating Voltage | Frequency | Voltage Distortion | Controlled Units |
|---|---|---|---|
| 220 V ±20% | 50 Hz / 60 Hz | ≤20% | ≤32 common / individual-phase intelligent capacitor units |
| Voltage | Current | Power Factor | Reactive Power |
|---|---|---|---|
| ±1% | ±1% | ±0.01 | ±2% |
| Model | Ambient Temperature | Relative Humidity | Altitude | Overall Dimensions | Panel Cutout |
|---|---|---|---|---|---|
| ZKY42 | -25°C to +65°C | ≤90% at 20°C | ≤2500 m | 120 × 120 × 80 mm | 113 × 113 mm |
| ZKY32 | -25°C to +55°C | 20-90% at 40°C | ≤2000 m | 120 × 120 × 100 mm | 112 × 112 mm |
Common Specifications
ZKY42 mounting depth: 70 mm.
Use the sampling and control wiring specified for the selected model.
You can also attach drawings, product photos or test reports, if available.
ZKY42 is suited to projects that need three-phase electrical measurements, harmonic display and compensation control. ZKY32 is intended for controlling compatible networked compensation units. Share the connected capacitor or switch model so we can check the configuration.
Yes. It displays voltage and current THD by phase, plus individual voltage and current harmonics from the 2nd to the 15th order.
Its manual lists Y-connected, Δ-connected and combined Y + Δ compensation. The selected setting must match the actual wiring.
The ZKY32 manual specifies up to 32 compatible common or individual-phase intelligent capacitor units.
It uses reactive power as the switching criterion and provides automatic and manual operating modes.