Capacitor Inrush Suppression
Dedicated current-limiting contacts and resistors suppress capacitor-bank making current. The specified inrush-current suppression capability is 20 Ie.
CJ19 Series
CJ19 Series Capacitor Switching Contactor
Contactors for switching low-voltage power factor correction capacitor banks in 50 Hz or 60 Hz AC systems.
Product Advantages
Capacitor switching capacities are grouped by their rated voltage.
Both groups use a 0-100 kvar scale. Ratingsapply at 380 V and 400 V respectively;compare models at the same voltage.
Separate capacitor capacities at 220 V or 240V are listed in the technical parameter table.
Check insulation rating, coil voltage,contactor. dimensions and mounting before selecting the contactor.
Dedicated current-limiting contacts and resistors suppress capacitor-bank making current. The specified inrush-current suppression capability is 20 Ie.
A current-limiting resistor reduces switching overvoltage when the capacitor bank is disconnected.
The direct-acting, double-break design uses contacts arranged in two layers, with a dedicated current-limiting arc chamber.
Model-specific capacitor capacities are provided at 220 or 240 V and 380 or 400 V, with ratings up to 90 kvar at 400 V.
Insulation covers the wiring terminals to reduce exposure of the connection points.
The rated coil voltage is marked on the coil terminals to help prevent incorrect connection.
Screw mounting and 35 mm or 75 mm DIN rails are available according to model. The 115 to 170 models support screws or two 35 mm rails.
The specified closing range is 85% to 110% of coil voltage Us, and the opening range is 20% to 75% Us.
Switching capacitor banks in 50 Hz or 60 Hz power factor correction systems
Applications with high inrush current during energization where a capacitor-duty contactor is specified
Low-voltage cabinets that switch capacitor steps with a CJ19 series contactor
Industrial feeders that use capacitor-duty contactors rather than general-purpose contactors
Building electrical rooms with low-voltage power factor correction banks
Installations within the stated frequency and operational-voltage limits
Boards that use screw mounting, 35 mm or 75 mm rails, or two 35 mm rails on the 115 to 170 models
Banks that need the specified 20 Ie inrush-current suppression capability
Panel builders selecting CJ19-25 to CJ19-170 by capacitor capacity and coil voltage
Replacing a general-purpose contactor where capacitor-bank making current requires a capacitor-duty device
| Rated Operational Voltage | Frequency | Inrush-current Suppression Capability |
|---|---|---|
| Up to 690 V AC | 50 / 60 Hz | 20 Ie |
| Model | Rated Current (A) AC-6b | Capacitor Capacity (kvar) 220 / 240 V Ratings | Capacitor Capacity (kvar) 380 / 400 V Ratings |
|---|---|---|---|
| CJ19-25 | 17 at 380 V | 6 at 220 V | 12.5 at 380 V |
| CJ19-32 | 23 at 380 V | 10 at 220 V | 20 at 380 V |
| CJ19-43 | 29 at 380 V | 15 at 220 V | 25 at 380 V |
| CJ19-63 | 43 at 380 V | 20 at 220 V | 37.3 at 380 V |
| CJ19-95 | 72.2 at 400 V | 35 at 240 V | 50 at 400 V |
| CJ19-115 | 87 at 400 V | 40 at 240 V | 60 at 400 V |
| CJ19-150 | 115 at 400 V | 46 at 240 V | 80 at 400 V |
| CJ19-170 | 130 at 400 V | 52 at 240 V | 90 at 400 V |
| Model | Rated Insulation Voltage (V) | Coil Power (VA) Making / Holding | Weight (kg) |
|---|---|---|---|
| CJ19-25 | 500 | 70/9.5 | 0.44 |
| CJ19-32 | 690 | 110/14 | 0.63 |
| CJ19-43 | 690 | 110/14 | 0.64 |
| CJ19-63 | 690 | 200/57 | 1.4 |
| CJ19-95 | 690 | 300/57 | 1.5 |
| CJ19-115 | 690 | 660/85.5 | 3.45 |
| CJ19-150 | 690 | 660/85.5 | 3.45 |
| CJ19-170 | 690 | 660/85.5 | 3.45 |
Common Specifications
Coil operating limits: closing at 85-110% Us; opening at 20-75% Us.
Specify the complete model, coil control voltage and frequency when ordering.
| Model | A max | B max | C max | D max | E | F | Mounting |
|---|---|---|---|---|---|---|---|
| CJ19-25 | 80 | 47 | 124 | 76 | 34/35 | 50/60 | Screw or 35 mm rail |
| CJ19-32 | 90 | 58 | 132 | 86 | 40 | 48 | Screw or 35 mm rail |
| CJ19-43 | 90 | 58 | 136 | 86 | 40 | 48 | Screw or 35 mm rail |
| CJ19-63 | 132 | 79 | 150 | - | - | - | Screw or 35/75 mm rail |
| CJ19-95 | 135 | 87 | 158 | - | - | - | Screw or 35/75 mm rail |
| CJ19-115~170 | 200 | 120 | 192 | 155 | - | - | Screw or two 35 mm rails |
Common Specifications
Dimensions A-F in mm.
| Ambient Temperature | 24-hour Average | Relative Humidity | Altitude |
|---|---|---|---|
| -5°C to +40°C | ≤+35°C | ≤50% at +40°C · Up to 90% at +20°C | ≤2000 m |
| Pollution Degree | Installation Category | Mounting Inclination |
|---|---|---|
| 3 | III | Within ±5° from vertical |
Common Specifications
Take measures against condensation caused by temperature changes.
Install where there is no significant shaking, impact or vibration.
You can also attach drawings, product photos or test reports, if available.
It is designed to switch low-voltage capacitor banks in reactive power compensation equipment. Its current-limiting structure reduces capacitor-bank making current and helps limit switching overvoltage.
For a capacitor branch, select a device rated for capacitor switching. The CJ19 information specifies an AC-6b capacitor-switching duty and gives capacitor capacity by model; selection should follow the actual operating voltage and bank kvar.
The specified product information states a rated operational voltage of up to 690 V at 50 Hz or 60 Hz. Confirm the selected model, coil voltage and capacitor-bank rating for the project.
Match the capacitor-bank kvar and operating voltage to the applicable model rating, then confirm the control-coil voltage, auxiliary-contact arrangement and mounting method. Do not select from the model number or rated current alone.
No. Its current-limiting contacts and resistor are designed to reduce making current and switching overvoltage. The complete branch still needs correctly selected capacitors, protection and wiring.
Provide the system voltage and frequency, capacitor kvar per switched step, required coil control voltage, auxiliary-contact requirement, mounting method and order quantity.