Three functions in one
Reactive power, harmonics and unbalance on one rack platform
LED-T Series
Advanced Static Var Generator
Dynamic reactive-power compensation, harmonic suppression and three-phase unbalance regulation in one rack platform.
Product Advantages
Related ProductsExplore other leenhoo power-quality products for harmonic mitigation and reactive-power compensation.
The ASVG separates reactive, harmonic and unbalanced components from load current, then actively injects controlled compensation current for dynamic tracking.
Configurable target power factor from -1 to 1.
Compensation coverage from the 2nd to the 13th harmonic.
Three-phase unbalance regulation for 3P3W and 3P4W systems.
Reactive power, harmonics and unbalance on one rack platform
Fast response <50 µs, full response <15 ms
2nd to the 13th, with per-order settings
30 / 50 / 75 / 100 kvar, up to 8 modules per monitoring unit
Target PF from -1 to 1
Ratios 150:5 to 30000:5, load side or grid side
7-inch color display, RS485 / Modbus
Overvoltage, undervoltage, short circuit and overcompensation
UPS and PDU reactive, unbalance and low-order harmonic support
Stable power factor and current balance for process loads
Welding and rectifier reactive, harmonic and unbalance compensation
Furnace and mill power-quality control
Pump and process-drive compensation
HVAC, lighting and transformer power-quality support
Imaging and critical-load current conditioning
Traction and station power-quality regulation
Inverter interface reactive and unbalance support
Drilling and process-drive compensation
| Parameter | Specification |
|---|---|
| Rated capacity | 30 / 50 / 75 / 100 kvar |
| Grid voltage | 380 V (80%-120%) |
| Grid frequency | 50 Hz ±5% |
| Grid structure | Three-phase three-wire / three-phase four-wire |
| Parallel operation | Up to 8 modules per monitoring unit; system supports parallel expansion |
| CT ratio range | 150:5 to 30000:5 |
| Parameter | Specification |
|---|---|
| Efficiency | ≥97% |
| Harmonic range | 2nd to 13th |
| Fast response | <50 µs |
| Full response | <15 ms |
| Target power factor | -1 to +1 |
| Cooling | Forced-air cooling |
| Noise | <65 dB |
| Parameter | Specification |
|---|---|
| Interface | RS485 |
| Protocol | Modbus |
| Monitoring | Centralized monitoring |
| Parameter | Specification |
|---|---|
| Protection functions | Overvoltage, undervoltage, short circuit, overcompensation |
| Alarm records | Up to 500 records |
| Parameter | Specification |
|---|---|
| Installation | Rack mounted |
| Finish | Black fine-texture finish (customizable) |
| Protection rating | IP20 |
| Altitude | ≤1500 m; 1% derating per 100 m from 1500 to 4000 m |
| Operating temperature | -10°C to +40°C; automatic derating above 40°C |
| Storage temperature | -20°C to +70°C |
| Relative humidity | Up to 95%, non-condensing |
| Rated Capacity | Dimensions W × D × H | Weight |
|---|---|---|
| 30 kvar | 350 × 465 × 88 mm | 14 kg |
| 50 kvar | 500 × 500 × 88 mm | 18 kg |
| 75 kvar | 500 × 500 × 88 mm | 18 kg |
| 100 kvar | 500 × 520 × 100 mm | 25 kg |
Common Specifications
Dimensions are shown as W × D × H.
Specifications are subject to change without notice. Confirm final model data before ordering.
You can also attach drawings, product photos or test reports, if available.
It provides dynamic reactive power compensation, harmonic compensation and three-phase unbalance regulation. These functions can be combined according to the selected operating mode.
The ASVG supports compensation from the 2nd to the 13th harmonic, with settings available for individual orders. The achievable result depends on the site’s harmonic conditions and system configuration.
Yes. The series includes models for three-phase three-wire (3P3W) and three-phase four-wire (3P4W) systems. Please confirm the wiring arrangement when selecting a model.
Rack-mounted modules are available in 30, 50, 75 and 100 kvar ratings. Up to eight modules can be connected to one monitoring unit for parallel operation.
The product introduction lists a fast response time of <50 μs and a full response time of <15 ms. It adjusts compensation current dynamically as the measured load changes.
Please share your system voltage and frequency, three-wire or four-wire arrangement, load details, and the power factor or harmonic issue you want to address. Existing measurements and CT information, if available, will help us recommend a suitable configuration.